Troubleshooting 04/2003 
 
SINAMICS G110    Operating Instructions 
58
 
6SL3298-0AA11-0BP0 
 
Checking for an ON Command 
If, for example, DIN0 on terminal 3 was set-up to give an ON command, the 
following procedure would allow the user to check that an ON command is present: 
1.  Ensure the BOP is connected to the inverter. 
2.  Set P0003 = 3. 
3.  Select parameter r0722. 
4.  The Seven-segment display will indicate the active bits as follows: 
 
 
 
5.  The lower mark on the right-hand side of the display indicates that DIN0 is 
active high, that is, an ON command is present. 
If the active high bit is not present it indicates that a ON command in not present. In 
such a case it is necessary to check the hardware configuration to ensure that 
DIN0 was, in fact, set-up for the ON command. 
In the case of ON/OFF control via the RS485 bus (USS protocol) the relevant bit 
(bit 02) of status word 1 (r0052) can be found in the following position: