  b) Keep buttons pressed not less than 2 seconds and then release the buttons; 
  c) On the display should appear “nAU”; 
  d) Then turn OFF the MCK-102-14.  Default factory settings are successfully restored. 
 
6 OPERATION MODES 
 
6.1 MCK-102-14 has 3 modes of operation: thermostat mode; defrost mode and the mode to control and 
set the required parameters. 
 
6.2 THERMOSTAT MODE 
6.2.1 In thermostat mode of operation  MCK-102-14  maintains necessary user-specified temperature 
inside the refrigeration chamber by operating the compressor. Please see below the scheme showing how 
MCK-102-14  relay output contacts operate by compressor depending on time and temperature inside the 
refrigeration chamber (scheme is shown for the default factory settings). 
6.2.2 Compressor operation.  Parameters  SP  (setting point) and dif  (differential) determine the 
temperature conditions in refrigerated chamber. If temperature value becomes higher then SP+dif  then the 
compressor will turn ON and will keep working until the temperature reaches the value of SP parameter. 
In case of malfunction or failure of the temperature sensors MCK-102-11 operates with the compressor in 
alarm mode using parameters  COn  and  COF  which determine the time intervals for ON/OFF state of the 
compressor. This alarm situation is indicated by alarm codes Er2 or Er3 shown on display. 
 
6.3 DEFROST MODE 
To perform the defrost of the refrigerated chamber MCK-102-14 turns OFF the compressor for the user 
preset time (parameter 
). Time interval between defrosts is determined by parameter . 
 
 
C02 – turn ON time delay for the compressor 
 – thermostat mode duration time 
 – defrost time 
      
  
 –setting point temperature adjusted by user 
  – differential 
         
 
 
 
relay of MCK-102-14  
 
 
 
6.4 FIRST START UP FEATURES 
When power supply is given to the input terminals of the MCK-102-14  on the display it is shown 
within first 5 seconds. Then further MCK-102-14 operation algorithm will depend on the value of  and 
 parameters.  
If 
=1 tttt: 
-  if =0 then after time defined by parameter +30 seconds MCK-102-14  will switch to thermostat 
mode; 
-  if  =1 then after time defined by parameter +30 seconds MCK-102-14  will switch to defrost 
mode. 
The first switching ON compressor will happen not early than time of autoreclosing (parameter 
)  or 
time of no load trip of compressor (parameter 
) depending on whether which time is more. 
If 
=0 autoreclosing time delay is equal 0. 
  
 
7 SYSTEM OF CONTROL OVER ALARM STATES