5. Setup 
Wire the power terminals only. After the power is turned on, the sensor input character and temperature 
unit are indicated on the PV display and the input range high limit value is indicated on the SV display for 
approximately 3 seconds. (Table 5-1) 
(If any other value is set during the scaling high limit setting, the set value is indicated on the SV display.) 
During this time, all outputs and the LED indicators are in OFF status. 
Control will then start indicating the input value (PV) on the PV display and main set value (SV) on the SV display. 
(While control output OFF function is working, 
  is indicated on the PV display.) 
(Table 5-1) 
 
 
Sensor input 
PV display  SV display 
PV display
SV display

 







PL-  
C (W/Re5-26) 
 
     
 
 
 
 
 
     
 
 
     
 
 
     
 
 
     
 
 
     
 
 
 
 
 
     
 
 
     
 
     
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
     
 
 
   
     
 
     
 
     
 
     
 
     
 
 
   
     
 
 
     
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Pt100 
 
JPt100 
 
 
 
 
 
 
 
 
 
 
 
     
 
 
 
     
 
 
     
 
 
 
 
 
 
 
 
     
 
4 to 20mA DC 
0 to 20mA DC 
0 to 1V DC 
0 to 5V DC 
0 to 10V DC 
1 to 5V DC 
 
 
 
 
 
 
 
 
 
 
 
   
 
Scaling high 
limit value 
 
 
   
 
 
 
 
   
 
Scaling high 
limit value 
5.1 Main setting mode 
Character 
(PV display) 
Name, Function, Setting range 
Default value 
(SV display)
 
SV 
0  
 
• Sets SV. 
 SV low limit to SV high limit, or Scaling low limit value to scaling high limit value 
5.2 Sub-setting mode 
Character 
(PV display)
 
Name, Function, Setting range 
Default value 
(SV display)
 
 
AT setting/Auto-reset setting 
 
 
 
 Selects auto-tuning Perform or auto-reset Perform. 
 If the auto-tuning is cancelled during the process, P, I and D values revert to the 
previous value. 
• When auto-tuning has not finished after 4 hours, it is cancelled automatically. 
 Auto-reset is cancelled in approximately 4 minutes. 
OUT1 proportional band setting 
10  
 
 Sets the proportional band for OUT1. 
 The control action becomes ON/OFF action when set to 0 or 0.0. 
 0 to 1000 (2000 ), With a decimal point: 0.0 to 999.9 ( ), DC input: 0.0 to 100.0% 
OUT2 proportional band setting 
1.0 times 
 
 Sets the proportional band for OUT2. 
OUT2 becomes ON/OFF action when set to 0.0. 
• Available only when Heating/Cooling control (option) is applied 
 0.0 to 10.0 times (multiplying factor to OUT1 proportional band)   
Integral time setting 
200 seconds 
 
 Sets the integral time. 
 Setting the value to 0 disables the function. 
 Auto-reset can be performed when PD is the control action (I=0). 
 0 to 1000 seconds 
Derivative time setting 
50 seconds 
 
 Sets the derivative time. 
 Setting the value to 0 disables the function. 
 0 to 300 seconds