Panasonic AKT4111100J Temperature Controller KT4 AKT4111100J Hoja De Datos

Los códigos de productos
AKT4111100J
Descargar
Página de 11
 
KT(AKT4,7,8,9)
 
4
 
 
 RATING & SPECIFICATIONS
 
Display
Specifications
KT4
KT8
KT9
KT7
Size
48 
 
×
 
 48mm
48 
 
×
 
 96mm
96 
 
×
 
 96mm
22.5 
 
×
 
 75mm
Supply voltage (Must be specified)
100 to 240V AC
24V AC/DC
Frequency
50/60Hz
Power consumption
Approx. 8VA
Approx. 8VA
Approx. 8VA
Approx. 6VA
Input type
Input range
Thermocouple
K
–200 to 1370°C (
–320 to 2500°F
)
–199.9 to 400.0°C (
–199.9 to 750.0°F
)
J
–200 to 1000°C (
–320 to 1800°F
)
R
0 to 1760°C (
0 to 3200°F
)
S
0 to 1760°C (
0 to 3200°F
)
B
0 to 1820°C (
0 to 3300°F
)
E
–200 to 800°C (
–320 to 1500°F
)
T
–199.9 to 400.0°C (
–199.9 to 750.0°F
)
N
–200 to 1300°C (
–320 to 2300°F
)
PL-II
0 to 1390°C (
0 to 2500°F
)
C (W/Re5-26)
0 to 2315°C (
0 to 4200°F
)
RTD
Pt100
–200 to 850°C (
–300 to 1500°F
)
–199.9 to 850.0°C (
–199.9 to 999.9°F
)
JPt100
–200 to 500°C (
–300 to 900°F
)
–199.9 to 500.0°C (
–199.9 to 900.0°F
)
DC Current
4 to 20mA DC
–1999 to 9999,  –199.9 to 999.9
–19.99 to 99.99,  –1.999 to 9.999
0 to 20mA DC
DC Voltage
0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
                    • Scaling and change to the decimal point position is possible for DC current and DC voltage input.
                    • DC current input is supported with an externally mounted 50
 
Ω
 
 shunt resistor (sold separately).
Multi-input
Thermocouple
                                            K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26)
                                            External resistor: Max. 100
 
Ω
 
 (max. 40
 
Ω
 
 external resistor for B input)
RTD
Pt100, JPt100 3-conductor system (Allowable input conductor resistance for each conductor: max. 10
 
Ω
 
)
DC current
                                     0 to 20 mA DC, 4 to 20 mA DC
                                     Input impedance: 50
 
Ω
 
 (Connect 50
 
Ω
 
 shunt resistor between input terminals.)
                                     Allowable input current: max. 50 mA (when 50
 
Ω
 
 shunt resistor is used)
DC voltage
           • 0 to 1V DC
             Input impedance: min. 1 M
 
Ω
 
, Allowable input voltage: max 5 V, Allowable signal source resistance: max. 2 k
 
Ω
 
           • 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
             Input impedance: min. 100 k
 
Ω
 
, Allowable input voltage: max 15 V, Allowable signal source resistance: max. 100
 
Ω
 
Control output
Relay contact
(Must 
be 
speci-
fied)
1a
1a1b
1a1b
1a
3A 250V AC (Resistive load), 1A 250V AC (Inductive load cos
 
φ
 
=0.4), Electric life: 100,000 times
Non-contact 
DC voltage
12 V DC, Max. load current: 40mA (Short-circuit protected)
DC current
4 to 20mADC Load resistance: Max. 550
 
Ω
 
Alarm output 1
                                      Relay contact 1a 3A 250VAC (Resistive load)
                                      Electric life: 100,000 times
Open collector, Control 
capacity: 24V DC 0.1A (Max.)
Control mode
Actions mentioned below can be selected by key operation. [Default PID] PID (with auto-tuning function), PI, PD (with manual 
reset function), P (with manual reset function), ON/OFF action
Accuracy
                         Thermocouple: Within ±0.2% of each input span ±1 digit or within ±2°C (
4°F
) whichever is greater
                                                  However, R and S input;  Within ±6°C (
12°F
) in the range of 0 to 200°C (
0 to 400°F
)
                                                  B input 0 to 300°C (
0 to 600°F
): Accuracy is not guaranteed.
                                                  K, J, E, and N input less than 0°C (
32°F
): Within ±0.4% of input span ±1 digit
                         RTD: Within ±0.1% of each input span ±1 digit or ±1°C (
2°F
) whichever is greater
                         DC current and DC voltage: Within ±0.2% of each input span ±1 digit
Sampling period
250ms
Hysteresis
                                Thermocouple & RTD: 0.1 to 100.0°C (°F)
                                DC current and DC voltage: 1 to 1000 (The decimal point place follows the selection)
Proportional band
                                       Thermocouple: 0 to 1000°C (0 to 2000°F)
                                       RTD: 0.0 to 999.9°C (0.0 to 999.9°F)
                                       DC current and DC voltage: 0.0 to 100.0%
0.0 to 110.0%
Integral time
0 to 1000 seconds
Derivative time
0 to 300 seconds
Proportional cycle
1 to 120 seconds
Allowable voltage fluctuation
When 100 to 240V AC;  85 to 264V AC  When 24V AC/DC;  20 to 28V AC/DC
Insulated resistance
500V DC  10M
 
Ω
 
 or greater
Breakdown voltage
1.5kV AC for 1min between input terminal and ground terminal,
between input terminal and power terminal
between power terminal and ground terminal
between output terminal and ground terminal, & between output terminal and power terminal
1.5KV AC for 1 min
between input terminal and 
power terminal, & between 
output terminal and power 
terminal
Malfunction vibration
10 to 55Hz (0.35mm) to each direction (120ms sweep) for 10min.
+2
0
KT_new.fm
4 y [ W Q O O Q N P O
P V œ @
j œ @
O P P