User interface
2.8 Menu bar
LOGO!Soft Comfort Online Help
100
Operating Instructions, 06/2014
2.8.5.34
Tools -> Ethernet Connections (0BA7 and 0BA8 only)
Use this menu command to configure the module address and build Ethernet connections for
the LOGO! Base Module.
①
Here you define the IP address of the LOGO! Base Module.
You first configure the IP address, subnet mask and gateway of the LOGO! Base Module
You first configure the IP address, subnet mask and gateway of the LOGO! Base Module
before making the Ethernet connections.
②
Here you define the Ethernet properties connected.
To add a ient/server connection, you can right click a connection item to enable the buttons:
To add a ient/server connection, you can right click a connection item to enable the buttons:
A LOGO! Base Module can support a maximum of eight network connections, which are
TCP/IP-based S7 communication connections to the following devices:
•
•
Additional LOGO! devices
•
SIMATIC S7 PLCs with Ethernet capability
•
A maximum of one SIMATIC HMI (Operator Panel) that supports Ethernet communication
with networked S7 PLCs
Note
For detailed information about S7 communication configurations between the LOGO! Base
For detailed information about S7 communication configurations between the LOGO! Base
Module, SIMATIC PLCs and HMIs, see FAQs under the Support selection at LOGO!
Website (
Each S7 connection can be configured to be a client or a server, in which the local IP/local
TSAP (Transmission Layer Service Access Point) and remote IP/remote TSAP are
configured respectively. The server is the data source side in communication, it sends
information that responds to the requests from the other side - the client.
To configure the client or server connections of each LOGO! connection, double-click the
To configure the client or server connections of each LOGO! connection, double-click the
connection.