5.3 Special functions
LOGO!Soft Comfort Online Help
216
Operating Instructions, 06/2014
LAD Editor/0BA4-0BA7:
The parameter box is not available in the LAD Editor or for 0BA4-0BA7
The parameter box is not available in the LAD Editor or for 0BA4-0BA7
devices.
Follow the below steps to create a reference:
1. Click the "Reference" button next to a parameter in the block properties
Follow the below steps to create a reference:
1. Click the "Reference" button next to a parameter in the block properties
window.
2. LOGO!Soft Comfort displays all the blocks available for providing the
reference parameter.
3. Select the block you want to refer to.
For example, if you click the "Reference" button for the Off-Delay parameter of
For example, if you click the "Reference" button for the Off-Delay parameter of
an Off-Delay timer, you can then choose a specific block to reuse the time
value of that timer.
LOGO! 0BA7 and LOGO! 0BA8 devices provide a timer reference function. With this
function, you can take the current time (Ta) of a timer as the reference value (C) in other
function blocks. The calculation of the reference value (C) follows the formula as shown
below:
Current time (Ta)
Time base
Reference value (C)
A : B
Hours (h : m)
C = A × 60 + B
A : B
Minutes (m : s)
C = A × 60 + B
A : B
Seconds (s: 1/100s)
C = A × 100 + B
Protection
If a Protection Active check box exists for the protection of a block parameter, you can
enable or lock the display and editing of this parameter in LOGO! configuration mode.
Retentivity
The switching state and counter values of SFBs can be retentive. This means that the
current data values are retained, for example after a power failure, so that the function is
resumed at the break position after power on. Hence, a timer is not reset, but instead the
time-to-go expires.
You must set the retentivity to enable this feature for the relevant function. There are two
You must set the retentivity to enable this feature for the relevant function. There are two
possible settings:
● On: Current data values are retained.
● Off: Current data values are not retained (default).
The Hours counter (Page 249) is an exception, because it is always retentive.
● On: Current data values are retained.
● Off: Current data values are not retained (default).
The Hours counter (Page 249) is an exception, because it is always retentive.