Timing diagram 
 
Description of function 
If input En is set, then the function issues one of four possible analog values V1 to V4 at the 
output AQ, depending on the inputs S1 and S2. 
If the input En is not set, then the function issues the analog value 0 at output AQ. 
Particular characteristics to be noted when configuring 
For help on analog block parameters, refer to the Basics (Page 286) section. 
Analog output 
If you connect this special function to a real analog output, then note that the analog output 
can only process values from 0 to 1000. To do this, connect an additional amplifier between 
the analog output of the special function and the real analog output. With this amplifier you 
standardize the output range of the special function to a value range of 0 to 1000. 
Example: additional amplifier behind an analog multiplexer.