Connection 
Description 
Input En 
A 0 to 1 transition at En (Enable) triggers the output of the message text. 
Input P 
P is the priority of the message text. 
0 is the lowest, 127 the highest priority. 
Ack: Acknowledgement of the message text 
Parameter 
Text: Input of the message text 
Par: Parameter or actual value of another, already configured , which can be 
displayed numerically or as a bar graph (see "Visible parameters or actual values") 
Time: Shows the continuously updated time-of-day 
Date: Shows the continuously updated date 
EnTime: Display of the time of the 0 to 1 transition of the signal at input En 
EnDate: Display of the date of the 0 to 1 transition of the signal at input En 
I/O Status Names: Display of a digital input or output status name, for example "On" 
or "Off". LOGO! 0BA7 devices can display the status names of following elements: 
• 
Digital inputs 
• 
Digital outputs 
• 
Flags 
• 
Cursor keys 
• 
LOGO! TD function keys 
• 
Shift register bits 
• 
Function block outputs 
Analog Input: Display of analog input value to the shown in message text and 
updated according to the analog time. 
Scale time (0BA7 only): Display of the actual value of a referenced function block as a 
time value scaled based on the timebase configured for the message text function 
block. Possible time display formats are as shown below: 
• 
hours : minutes : seconds . milliseconds 
• 
hours : minutes : seconds 
• 
hours : minutes 
• 
hours 
(for example, "01: 20 : 15 .15") 
Symbol (0BA7 only): Display of characters selected from the supported character sets 
Output Q 