Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 Hoja De Datos
Los códigos de productos
6ED1057-3BA00-0AA8
LOGO! installation and wiring
2.1 Modular LOGO! setup
LOGO!
30
Manual, 06/2014, A5E33039675
High-speed/optimal communication performance
For optimal and high-speed communication performance between the LOGO! Base Module
and the various modules, install the digital modules first, then the analog modules (as the
examples above show). (The special function PI controller is an exception: the AI used for
the value PV should be on the LOGO! Base Module or an analog input module adjacent to
the LOGO! Base Module).
You install the LOGO! TDE module separately and connect it to the LOGO! Base Module
You install the LOGO! TDE module separately and connect it to the LOGO! Base Module
with the Ethernet interface.
2.1.3
Setup with different voltage classes
Rules
You can only connect digital modules to devices of the same voltage class.
You can connect analog and communications modules to devices of any voltage class.
You can replace two similar DM8 expansion modules by one appropriate DM16 expansion
You can connect analog and communications modules to devices of any voltage class.
You can replace two similar DM8 expansion modules by one appropriate DM16 expansion
module (and vice versa) without having to change the circuit program.
Note
You can only replace two DM8 12/24R modules with one DM16 24R module if the power
You can only replace two DM8 12/24R modules with one DM16 24R module if the power
supply is 24 VDC.
You can only replace two DM8 24R modules with one DM16 24R module if they use DC and
You can only replace two DM8 24R modules with one DM16 24R module if they use DC and
positive-voltage input.
Overview: Connecting an expansion module to the LOGO! Base Module
In the following tables, "X" means that the connection is possible; "-" means that the
connection is not possible.
LOGO! Base Module
Expansion modules
DM8 12/24R,
DM16
24R
DM8 24,
DM16 24
DM 8
24R
DM8
230R,
DM16
230R
AM2,
AM2 RTD, AM2
AQ
LOGO! 12/24RCE
x
x
x
-
x
LOGO! 230RCE
-
-
-
x
x
LOGO! 24CE
x
x
x
-
x
LOGO! 24RCE
x
x
x
-
x
LOGO! 12/24RCEo
x
x
x
-
x
LOGO! 24CEo
x
x
x
-
x
LOGO! 24RCEo
x
x
x
-
x
LOGO! 230RCEo
-
-
-
x
x