Phoenix Contact Inline terminal IB IL 24 DO 2-2A-PAC 2861263 2861263 Hoja De Datos

Los códigos de productos
2861263
Descargar
Página de 7
Nov 14, 2013    2 / 7
Technical data
General
Weight
46 g
Note on weight specifications
Without plug
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Diagnostics messages
Short-circuit / overload of the digital outputs Error message in the
diagnostic code (bus) and display (2 Hz) via the LED (D) on the
module
Interfaces
Fieldbus system
Lokalbus
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Communications power U
L
7.5 V (via voltage jumper)
Current consumption
max. 35 mA (from the local bus)
Inline potentials
Communications power U
L
7.5 V DC
Current consumption from U
L
max. 35 mA
Main circuit supply U
M
24 V DC
Segment supply voltage U
S
24 V DC (nominal value)
Current consumption from U
S
max. 4 A
Digital outputs
Output name
Digital outputs
Connection method
Spring-cage connection
Connection method
2, 3, 4-wire
Number of outputs
2
Protective circuit
Overload protection, short-circuit protection of outputs
Output voltage
24 V (U
S
 - 1 V)
Nominal output voltage
24 V DC (voltage difference at I
nom
 ≤ 1 V)
Maximum output current per channel
2 A
Maximum output current per module
4 A
Nominal load, inductive
48 W
Nominal load, lamp
48 W