Fanox 41000 ELR-3C Differential Relay 41000 Hoja De Datos

Los códigos de productos
41000
Descargar
Página de 3
47
WIRING DIAGRAM (mm)
EARTH LEAKAGE PROTECTION
MODELS
ELR-B
ELR-3C
Sensitivity
0,3 A or 0,5 A
Adjustable from 0,025 A to 25 A
Trip time delay
0,02 s or 0,5 s
Adjustable from 0,02 s to 5 s
Aux. voltage supply  50/60 Hz
24-48 Vdc, ac
115 Vdc, ac
230-400 Vac
24-48 Vdc, ac
115 Vdc, ac
230-400 Vac
Code
41012
41010
41005
41000
CHARACTERISTICS
Toroidal transformer
In combination with CT-1
Max. length between relay and 
transformer
20 m with cables twisted
Reset mode
Automatic, manual and remote (in manual mode disconnect the aux. supply during 1s)
Signalling LED’s
2 LED’s: ON + Trip
Output contacts mode
Normally de-energized
Output contacts
1 change over NO-NC
Switching power (resistive load)
5A - 250V
Maximum terminal section
2,5 mm
2
Maximum consumption
3 VA
Modular size
3 modules x 17,5 mm = 52,5 mm
Frequency
50/60 Hz
Protection degree / weight
IP-20 / 0,2 kg
Storage / operation temperature
-10°C +60°C
Standards
IEC 41-1, IEC 255, VDE 0664, EN 50081-1, EN 50082-2
DIMENSIONS (mm)
ELR-B
ELR-3C
        














•  Electronic relays with adjustable delay time and sensitivity.
• Suitable for direct pulse current.
• Immune to external disturbances.
• To be used with CT-1 transformers.
• Modular size. DIN rail mounting.
• Sealable front cover.
•  Electronic relays with adjustable delay time and sensitivity.
• Suitable for direct pulse current.
• Immune to external disturbances.
• To be used with CT-1 transformers.
• Modular size. DIN rail mounting.
• Sealable front cover.
RELAY WITH ADJUSTABLE DELAY TIME AND SENSITIVITY
MULTIRANGE RELAY
Earth leakage relays WITHOUT BUILT-IN toroidal transformer
www.fanox.com
fanox@fanox.com
Tlf. +34 94 471 14 09
Fax +34 94 471 05 92
10/2010/D00