Tele 1340300 E1PF400VSY01 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 1340300 Hoja De Datos
Los códigos de productos
1340300
Änderungen und Irrtümer vorbehalten
Subject to alterations and errors
Subject to alterations and errors
www.tele-power-net.com
Phase sequence monitoring
When all the phases are connected in the correct sequence and the
measured asymmetry is less than the fixed value, the output relay
switches into on-position (yellow LED illuminated). When the phase
sequence changes, the output relay switches into off-position (yellow
LED not illuminated).
When all the phases are connected in the correct sequence and the
measured asymmetry is less than the fixed value, the output relay
switches into on-position (yellow LED illuminated). When the phase
sequence changes, the output relay switches into off-position (yellow
LED not illuminated).
L1 L2
11
12 14
R
N L3
12 14
11
L1
L2
L3
N
3N~
Phase failure monitoring
The output relay switches into off-position (yellow LED not illuminated),
when one of the three phases fails.
The output relay switches into off-position (yellow LED not illuminated),
when one of the three phases fails.
Asymmetry monitoring
The output relay R switches into off-position (yellow LED not illuminated)
when the asymmetrie exceeds the value set at the ASYM-regulator.
Reverse voltages of a consumer (e.g. a motor which continues to run on
two phases only) do not effect the disconnection.
The output relay R switches into off-position (yellow LED not illuminated)
when the asymmetrie exceeds the value set at the ASYM-regulator.
Reverse voltages of a consumer (e.g. a motor which continues to run on
two phases only) do not effect the disconnection.
Connections
Ordering informations
Dimensions
17,5mm
60mm
87mm
44mm
5mm
45mm
Types
Nominal voltage Un
Threshold voltage Us
Part. Nr. (PQ 1)
E1PF400VSY01
3(N)~400/230V
Asymmetrie 5%...25%
1340300
LEDs
U, Rel.
Functions
E1PF