without control signal
Asymmetrical recycler
without control signal
Mono-function
with control signal (S)
Type
83.11
(AI)
On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI)
Interval.
Apply power to timer. Output contacts transfer immediately. 
After the preset time has elapsed, contacts reset.
(BI)
Power off-delay (True off-delay).
Apply power to timer (minimum 500 ms). Output contacts
transfer immediately. Removal of power initiates the preset
delay, after which time the output contacts reset.
(SD) 
Star-delta.
Apply power to timer. The star contact (   ) closes immediately.
After preset delay has elapsed the star contact (   ) resets. 
After a further time (settable from 0.05s to 1s) the delta 
contact ( Δ ) closes and remains in that position, until reset on
power off.
(BE)
Off-delay with control signal.
Power is permenently applied to the timer.
The output contacts transfer immediately on closure of the 
control signal (S). Opening the control signal initiates the 
preset delay, after which time the output contacts reset.
(LI) 
Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ON and OFF times are independently 
adjustable.
(PI) 
Asymmetrical flasher (starting pulse off) - (Z1-Z2 linked).
Apply power to timer. Output contacts transfer after time T1
has elapsed and cycle between OFF and ON for as long as
power is applied. The ON and OFF times are independently
adjustable.
(LE) 
Asymmetrical flasher (starting pulse on) with control 
signal - (Z1-Z2 open).
Power is permenently applied to the timer.
Closing control signal (S) causes the output contacts to 
transfer immediately and cycle between ON and OFF, 
until opened.
(PE)
Asymmetrical flasher (starting pulse off) with control 
signal - (Z1-Z2 linked).
Power is permenently applied to the timer.
Closing the control signal (S) initiates delay T1 after which the
output contacts transfer and continue to cycle between OFF
and ON, until the control signal is opened.
83.11
83.21
83.82
83.41
83.91
Z1-Z2 open: (LI) function
Z1-Z2 linked: (PI) function
Z1-Z2 open: (LE) function
Z1-Z2 linked: (PE) function
83.91
Wiring diagram 
Functions
83 Series - Modular timers 16 A
83.62
83.21
83.82
83.41
83.62
8
with control signal
= Supply voltage
= Signal switch
= Output contact