Valve Regulated Lead-Acid Batteries
29
Valve Regulated Lead-Acid Batteries
9 | Battery Selection Chart
Method of battery selection (Estimation of initial discharge
time)
(1) Determine discharge current.
(2) Determine duration of discharge required.
(3) Select batteries from the selection chart below. Then,
select a battery which meets the specification of the
equipment in which the battery is loaded such as voltage,
dimensions and mass, from the “Battery Index” on page
28 to 29.
(4) Example
– Use condition: 2.9 A, 1.5 hours, 12 V; space allowable
100 mm x 160 mm x 105 mm
– 7.2 Ah is selected in the step (3).
– LC-R127R2P 94 mm x 151 mm x 100 mm is selected in
the step (4).
(5) Refer to individual data sheets for detailed discharge
characteristics of the battery.
(Note) Data given are the average values obtained within
three cycles of charge/discharge, not the minimum values.
VRLA battery
for main power applications
VRLA battery
for standby power applications
(2.2 Ah to 28 Ah)
(mA)
(hour)
Duration of dischar
ge
Discharge current
(A)
30
20
15
10
5
4
3
2
1
50
40
30
20
<Temperature 20°C>
LC-XC1228AP
50 100 200 300
500 1 2 3 4 5 10 20 30 50
Minute
LC-XC1238AP
(mA)
(hour)
Duration of dischar
ge
Discharge current
(A)
30
20
15
10
5
4
3
2
1
50
40
30
20
<Temperature 20°C>
30 50
100 200
300
500
1
2 3 4 5 10 20 30
Minute
LC-X1228AP
LC-X1228P
LC-X1228P
LC-X1224AP
LC-X1224P
LC-X1224P
LC-X1220
LC-RD1217P/ LC-PD1217P
LC-RD1217AP/ LC-PD1217AP
LC-RD1217AP/ LC-PD1217AP
LC-R0612P
LC-RA1212P
LC-P0612P
LC-RA1212P
LC-P0612P
LC-R067R2P
LC-R127R2P
LC-P067R2P
LC-P127R2P
LC-R127R2P
LC-P067R2P
LC-P127R2P
UP-RW1245P1
LC-R067P
LC-R127P
LC-R127P
LC-R063R4P
LC-R123R4P
LC-R123R4P
LC-R064R5P
LC-R122R2P
/ LC-CA1212
/ LC-XD1217P
LC-CA1215
LC-CA1216
LC-XC1222
9 | Battery Selection Chart
VRLA battery
for standby power applications
(high-power for UPS)
(mA)
(hour)
Duration of dischar
ge
Discharge current
(A)
Minute
1500
1200
1000
1000
500
300
100
50
30
10
5
3
30 50 100 200 300 500 1 2 3 4 5 10 20 30
UP-RW1220P1
UP-RW1245P1
UP-RWA1232P1
<Temperature 20°C>
LC-R1233P
)r
u
o
H(
)
et
u
ni
M(
Dur
ation of discharge
30
20
15
10
5
4
4
3
2
1.5
1
50
40
40
30
20
10
5
3
300 500 1 3 5 10 30 50 100 300 500 1000
300 500 1 3 5 10 30 50 100 300 500 1000
)
A
(
)
A
m
(
Discharge current
<Temperature 20˚C>
LC-X1265P
LC-X1242AP
LC-X1242P
LC-X1242P
LC-X1238AP
LC-X1238P
LC-X1238P
VRLA battery
for standby power applications
(100Ah)
VRLA battery
for standby power applications
(33Ah to 65Ah)
LC-XB12100P
<Temperature 20˚C>
1 3 5 10 30 50 100 300 500 1000
Discharge current
(A)
30
20
15
10
5
4
4
3
2
1.5
1
50
40
40
30
20
10
5
3
Dur
ation of discharge
)r
u
o
H(
)
et
u
ni
M(
LC-X12120P
LC-X06200P