Baco Limit switch BANC54DX80 1 pc(s) 227553 Hoja De Datos

Los códigos de productos
227553
Descargar
Página de 8
225
Cam Switches
Technical Specifications
IEC Characteristics
PR 12
PR 17
PR 21
PR 26
PR 40
PR 63
PR 125
PR 160
>
Performance in AC 3 - cont.
- In HP (for reference)
- 3 x 230 V
4
5.5
5.5
7.5
15
20
-
-
- 3 x 400 V
5.5
10
10
15
25
30
-
-
- 3 x 500 V
7.5
10
10
15
25
30
-
-
- 3 x 690 V
4
10
10
15
25
30
-
-
>
Rated insulation voltage Ui (V)
690
690
690
690
690
690
690
690
- Max. rated voltage Ue(v) IEC
690
690
690
690
690
690
690
690
- CSA (Canada)
600
600
600
600
600
600
600
600
- UL (USA)
600
600
600
600
600
600
600
600
>
Rated short time withstand current  
Icw (A) for 1 sec
250
400
420
800
1000
1000
2000
2400
>
Maximum wire size (mm2)
- rigid
4
6
/
4
(1)
6/4
(1)
6
16
16
ø 8 screw for eyelet
- flexible
2.5
4
4
6
16
16
ø 8 screw for eyelet
>
Maximum wire size (AWG)
- rigid
10
8
/
10
(1)
8/10
(1)
8
6
6
- flexible
14
12
12
8
6
6
(1): These values correspond to terminals with jumpers
>
Mechanical durability
1,250,000
operations, maximum rate 150 operations per hour
>
Operating temperature limits 
- 20°C to + 70°C - 4°F to + 158°F (beyond these limits consult us)
>
Rated operating current in DC-1
low inductive loads
(< 1 ms)
Rated operating current Ie (A) 24 V DC
16
20
25
32
50
80
-
-
Ie (A): rated current for breaking 1 contact. For higher voltages you must use a reduction coefficient K in the following graph
K
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
24
48
60
95
120
220
440
volts
breaking 1 contact 
breaking 2 contacts in series
reduction coefficient K for rated operating current in DC-1 continuous current
PR 12
PR 17
PR 21
PR 26
PR 40
PR 63
PR 125
PR 160