Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manual De Usuario

Los códigos de productos
6AV6651-7KA01-3AA4
Descargar
Página de 364
 
Technical specifications 
 
A.4 Specifications for the digital inputs and outputs 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
305
 
Technical data 
Relay  
(CPU and SM) 
24 VDC  
(CPU, SM, and SB) 
200 KHZ 24 VDC  
(SB) 
Isolation groups 
 
CPU 1211C: 1 
 
CPU 1212C: 2 
 
CPU 1214C: 2 
 
CPU 1215C: 2 
 
SM DQ 8: 2 
 
SM DQ 8 Changeover:8 
 
SM DQ 16: 4 
 
CPU: 1 
 
SB: 1 
 
SM (DQ 8): 1 
 
SM (DQ 16): 1 
1
5
 
Isolation resistance 
100 MΩ min. when new 
N/A 
N/A 
Isolation between open 
contacts 
750 VAC for 1 minute 
N/A 
N/A 
Current per common 
CPU:  
SM Relay:  
 
SM 1222: 10 A (DQ 8 
and DQ 16) 
 
SM 1223 DI 8 / DQ 8 
Relay: 10 A 
 
SM 1223 DI 16 / DQ 16 
Relay: 8 A 
CPU:  
 
SB: 1 A 
 
SM DQ 8: 4 A 
 
SM DQ 16: 8 A 
0.4 A 
Inductive clamp voltage 
N/A 
L+ minus 48 V,  
1 W dissipation 
None 
Maximum relay switching 
frequency 
1 Hz 
N/A 
N/A 
Switching delay 
10 ms max. 
CPU:  
 
Qa.0 to Qa.3: 1.0 μs 
max., off-to-on 3.0 μs 
max., on-to-off 
 
Qa.4 to Qb.1: 50 μs 
max., off-to-on  
200 μs max., on-to-off 
SB: 2 μs max. off-to-on;  
10 μs max. on-to-off 
SM: 50 μs max. off-to-on 
200 μs max. on-to-off 
1.5 μs + 300  s rise 
1
 
1.5 μs + 300 ns fall 
1
 
200 ns + 300 ns rise 
2
 
200 ns + 300 ns fall 
2
 
Lifetime mechanical (no load)  Relay: 10,000,000 
open/close cycles 
N/A 
N/A 
Lifetime contacts at rated load  Relay: 100,000 open/close 
cycles 
N/A 
N/A