Salicru SLC-700-TWIN RT (B1) 698AA-06 + 2X698BT-01 Hoja De Datos
Los códigos de productos
698AA-06 + 2X698BT-01
SLC TWIN RT
Rack/tower On-line UPS 700 VA - 10,000 VA
REF. JM820C01 CODE 401AB000615 ED. JANUARY 2015 UNINTERRUPTIBLE POWER SUPPLY (UPS)
TECHNICAL SPECIFICATIONS
Data may change without previous notice.
IEC type AC outputs.
Emergency Power Off (EPO)/Digital input.
USB port.
AC input.
Dry contacts.
SNMP/relays smart slot.
RS-232 interface.
Parallel port.
Maintenance bypass.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Connections
Communications
Higher output power
· RS-232 interface.
· USB interface.
· SNMP/relays smart slot.
· Monitoring and management software for Win-
dows, Linux, Unix and Mac.
· SNMP/web adapter.
(1)
· AS-400 card.
(1)
· MODBUS protocol.
(1)
· Temperature-humidity sensor.
(1)
Power Factor (PF) = 0.9.
+30% of active power over other UPS with FP = 0.7.
+efficiency (98%) with Eco-mode function.
Dimensions and weight for standard back-up models
RANGE
WARRANTY
(*)
2
YEARS
ASK FOR LOCAL CONDITIONS
(*) Units ≥ 4 kVA: 1 year warranty
www.linkedin.com/company/salicru
@salicru_SA
(*) Spain only (**) Rest of the world
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · salicru@salicru.com
902 48 24 00
*
+34 93 848 24 00
**
WWW.SALICRU.COM
MODEL
SLC TWIN RT 0,7 - 3 kVA SLC TWIN RT 4 - 10 kVA
FORMAT
Tower / Rack
TECHNOLOGY
On-line, double conversion, PFC, double DC bus
INPUT
Nominal voltage
208 / 220 / 230 / 240 V
(1)
Voltage range
120 ÷ 276 V
(2)
Frequency
50 / 60 Hz
Frequency range
±10%
Power factor
≥0.99
Total Harmonic Distortion (THDi)
<5%
OUTPUT
Power factor
0.9
Nominal voltage
208 / 220 / 230 / 240 V
(1)
Voltage accuracy
±1%
Maximum slew rate
1 Hz/s
Frequency
synchronization
mains present
±10%
free running
±0.2 Hz
±0.1 Hz
Efficiency
>89%
(3)
>93%
Total Harmonic Distortion (THDv)
≤2% linear load; ≤5% non-linear load (according to EN 62040-3)
Admissible overload
(normal mode)
Up to 130% during 12 s;
150% during 1.5 s
Up to 125% during 2 min;
150% during 30 s
Crest factor
3 to 1
Paralel
No
Yes, up to 2 units
BYPASS
Nominal voltage
208 / 220 / 230 / 240 V
(1)
Admissible frequency range
50 / 60 Hz ±10 Hz
Independent bypass line
No
Yes
MANUAL BYPASS
No
Yes (‘make before break’ type)
BATTERY
Type
Sealed lead acid, AGM and free maintenance
Protection
Against overvoltages, under voltages and alternating current component
CHARGER
Charge type
I/U (Constant power/Constant voltage)
Recharging time
3 hours at 90%
Compensation voltage for temperature
Yes
COMMUNICATION
Ports
RS-232 and USB
Monitoring software
For Windows, Unix, Linux and Mac.
Emergency Power Off (E.P.O.)
Yes
FUNCTION MODES
Eco-mode
Yes, up to 98% efficiency
Starting free running (Cold Start)
Yes
Frequency converter
Yes
(4)
INDICATORS
Directable LCD display
GENERALS
Operating temperature
0º C ÷ +40º C
0º C ÷ +45º C
Relative humidity
Up to 95%, non-condensing
Operating altitude
1000 m.a.s.l. (degradation power up to 5000 m.a.s.l.)
Acoustic noise @ 1 metre
<45 dB
(5)
<55 dB
STANDARDS
Safety
EN-62040-1; EN-60950-1; EN-60529
Electromagnetic compatibility (EMC)
EN-62040-2
Operating
VFI according to EN-62040-3
Quality and environmental
ISO 9001 and ISO 14001
Model
Apparent
power (VA)
Active
power (W)
SLC-700-TWIN RT
700
630
SLC-1000-TWIN RT
1,000
900
SLC-1500-TWIN RT
1,500
1,350
SLC-2000-TWIN RT
2,000
1,800
SLC-3000-TWIN RT
3,000
2,700
SLC-4000-TWIN RT
4,000
3,600
SLC-5000-TWIN RT
5,000
4,500
SLC-6000-TWIN RT
6,000
5,400
SLC-8000-TWIN RT
8,000
7,200
SLC-10000-TWIN RT
10,000
9,000
(1) Optional
MODEL
POWER
(VA / W)
DIMENSIONS
(D x W x H mm.)
WEIGHT
(Kg)
SLC-700-TWIN RT
700 / 630
435 x 438 x 89 (2U)
14
SLC-1000-TWIN RT
1,000 / 900
435 x 438 x 89 (2U)
15
SLC-1500-TWIN RT
1,500 / 1,350
435 x 438 x 89 (2U)
19
SLC-2000-TWIN RT
2,000 / 1,800
435 x 438 x 89 (2U)
20
SLC-3000-TWIN RT
3,000 / 2,700
608 x 438 x 89 (2U)
29
SLC-4000-TWIN RT
4,000 / 3,600
630 x 438 x 133 (3U)
45
SLC-5000-TWIN RT
5,000 / 4,500
630 x 438 x 133 (3U)
46
SLC-6000-TWIN RT
6,000 / 5,400
630 x 438 x 133 (3U)
47
SLC-8000-TWIN RT
8,000 / 7,200
640 x 438 x 223 (5U)
82
SLC-10000-TWIN RT
10,000 / 9,000
640 x 438 x 223 (5U)
83
(1) Power reduction at 208 V for
units ≥ 4 kVA
(2) With 50% of load
(3) For units of 700 and 1000 VA >87%
(4) Power reduction of 30%
(5) Models > 1500 VA is < 50 dB
SLC-6000-TWIN RT
SLC-1500-TWIN RT