TROUBLESHOOTING (cont.)
Check for "ON" position or no 
continuity - replace switch.
Clean filter and fins or replace 
condenser filter. (Filter not supplied 
on some machines).
A) Check for 120V or 230V AC. 
Replace fan motor or check fan 
blades for obstructions.
B) Check compressor LED on circuit 
board. If ON, relay coil should have 
power (120 or 230 VAC).
Check compressor relay coil for 120 
or 230vac.
NOTE: Always check power with 
coil attached. If compressor LED is 
ON and no 120 or 230vac - replace 
board. If yes, 120 or 230vac - replace 
relay.
Note: Relay contacts are normally 
open.
Check compressor thermal 
overload (N/C). If open check for 
dirty condenser filter or adequate 
ventilation and space around 
machine.
Check refrigeration system for leaks 
and proper charge.
(A) Set switch to ON position.
(B) Check switch and harness for 
proper continuity.
Check all previous items that 
pretain to refrigeration or cold water 
recirculation
1. Compressor ON/OFF switch.
2. Dirty condenser filter or fins.
3. Condenser fan not running.
4. Compressor relay not activating.
5. Compressor not running.
6. Compressor running and not 
cooling.
1. Check Dispense Lockout switch.
1. Refrigeration or cold water 
recirculation system.
Refrigeration
Dispense stations not working.
Note: Cooling failure or excessive 
bath and cabinet temperatures for 
more than 4 hours will result in 
dispense lockout or no dispense.
Dispenser Locked Out
Dispense stations not working.
Cooling system failure.