Burnham Series C Power Flame Hoja De Datos
Power Flame Burner Equipment
Equipment
Fuel
Description
Control Cabinet
Gas, #2 Oil, Gas/#2 Oil NEMA 1A with hinged door.
Control Voltage Transformer
Gas, #2 Oil, Gas/#2 Oil Included with all but 115/60/1 burners.
Motor Starter
Gas, #2 Oil, Gas/#2 Oil Contactor on all single phase motors. Magnetic starter with overload protection on 3-
phase motors.
Fusing
Gas, #2 Oil, Gas/#2 Oil Control circuit only.
Ignition
Gas and Gas/#2 Oil
Gas/Electric pilot.
#2 Oil
Direct spark.
Gas, #2 Oil, Gas/#2 Oil Two [power on and fuel on].
Full Mod
Four [power on, fuel on, flame failure, and call for heat]
Gas,#2 Oil, Gas/#2 Oil All models.
#2 Oil
C-70 and larger
Gas Train
Gas and Gas/#2 Oil
UL gas train for minimum inlet pressure indicated on Burner Information table.
Shipped unassembled and consisting of the following:
Shipped unassembled and consisting of the following:
z
Manual shut-off valve.
z
Gas pressure regulator
z
Manual leak test valve.
z
Automatic gas valve: Diaphragm type with On-Off sequence. Solenoid type
all others.
z
Safety gas valve: Solenoid type.
z
High and Low gas pressure switches: Models C-60 and larger.
Oil Pump
#2 Oil and Gas/#2 Oil
Integral with burner.
Pilot Gas Controls
Gas, #2 Oil, Gas/#2 Oil All models with gas/electric pilot have manual pilot shut-off valve, soft seat low gas
pressure regulator and solenoid gas valve.
Fuel Changeover
Gas/#2 Oil
Manual switch.
5/26/2010
Signal Lights
Air Flow Safety Switch
C SERIES