Periodic maintenance  67 
Component to be inspected 
Task 
Frequency 
Capable Party 
— 
Inspect the door operation and 
inspect the door gaskets for water 
and air leaks. 
Annually 
Qualified personnel 
— 
Visually inspect the paint. Perform 
prep and touch-up as necessary. 
Annually 
Qualified personnel 
 
 
Life safety 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
Manual EPO shunt trip 
EPO FUNCTIONAL TEST 
Manually initiate EPO with the 
internal and external push buttons 
(if installed) in succession. (Verify 
all shunt-trips on all panels trip.) 
Annually 
Qualified personnel 
Thermal EPO shunt trip 
EPO FUNCTIONAL TEST 
Initiate a thermal (automatic) EPO 
shutdown via the EPO 
temperature switches located in 
the hot aisle. (Verify all shunt-trips 
on all panels trip.) 
Annually 
Qualified personnel 
EPO System Test 
EPO NON-FUNCTIONAL TEST 
Mode Key Switch Test - rotate 
keyed switch through all modes. 
ARMED MODE - Verify: 
 
Power Indicator - White 
 
Armed Light - White 
BYPASS MODE - Verify 
 
Bypass Light - Green 
TEST MODE - Verify: 
 
Test Light - Amber 
Press EPO button (each in 
succession) and thermal trip to 
verify: 
 
Reset Light - White 
 
Audible alarm 
 
Visual lamp indicator 
Replace light upon failure 
Annually 
Qualified personnel 
Emergency Lighting 
Verify emergency lighting is 
visible when all lighting is off and 
the POD doors are shut. 
Every 2 years 
Qualified personnel 
Exit signs 
Visually inspect Tritium exit signs 
for operation or damage. 
Replace as necessary. 
Every 2 years 
Qualified personnel 
Emergency egress 
Personnel door emergency egress 
panic bars. (Visual and 
operational inspection.) 
Bi-annually 
Qualified personnel