Site requirements  13 
Requirement   
Specification 
Connection 
1.9 cm (.75 in) G 
Adapter to 1.9 cm (.75 in) FPS 
Hardness 
No greater than 40°fH (equal to 400 ppm of CaCO
3
Conductivity 
100 to 1250 μS/cm 
Organic compounds 
None 
Type of water 
Drinking water. Do not use de-mineralized or softened water. 
Instant water fill flow 
rate 
0.6 lpm (0.16 gpm) 
Humidifier 
For the exact requirements, see the humidifier documentation. 
  
 
IMPORTANT:
  If your water is out of range, consult a water quality expert. 
 
   
 
IMPORTANT:
  You must provide a humidification water supply isolation valve that is external to 
the HP POD 40c G2.  
  
In addition to the previous requirements, observe the following requirements and recommendations: 
 
Do not treat the water with softeners. Softeners can produce foam, which affects the operation of the 
unit. 
 
Do not use well water, industrial water, water from cooling circuits, or water contaminated by any 
chemicals or bacteria. 
 
Do not add potential irritants to the water, such as disinfectants or anti-corrosive compounds. 
 
The manufacturer recommends installing an in-line filter for the water supply. It is your responsibility to 
determine if a filter should be installed, and if so, its location. The filter cannot be installed inside the HP 
POD 40c G2 and must be compatible with the type of humidifier that is installed. 
For more information, see the HP Performance Optimized Datacenter 40c G2 Maintenance and Service 
Guide
 
Drainage 
 
Requirement 
Location 
Specification 
Condensate drains 
Hot aisle side (2) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
Humidifier drains 
Cold aisle side (1) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
 
 
Chilled water supply 
The following are the water quality requirements and specifications: 
 
Closed-loop water must not contain any lime scale deposits or loose debris. 
 
The temperature of the chilled water supplied to the HP POD 40c G2 must be 12ºC to 24ºC (55ºF to 
75ºF). 
  
 
CAUTION: 
 Freezing water can cause a blockage and damage to the unit. In outside locations 
that are subject to freezing temperatures, an additive such as glycol might be necessary to lower 
the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP 
POD 40c G2 must be de-rated accordingly.