EXCEL 500/600 INSTALLATION INSTRUCTIONS 
ground 
Vi 
10 Vdc 
Immersion temperature sensor VF 100 
Air duct temperature sensor LF 100 
25K ohm 
Wind sensor: 
Wind sensor WS21. 
Further connections: 
200K ohm 
Temperature sensor terminal TF26 
Table 15. Accuracy of analog input sensors 
Fig. 75. Analog input / low-impedance sensors 
Pull-Up Resistor Handling when Using Analog Inputs as 
Digital Inputs (O.S. 2.03.xx) 
When the input is identified as a DI point in CARE (DI 
subtype AI), the internal pull-up resistor is enabled. 
10 Vdc 
25K ohm 
200K ohm 
Fig. 76. Analog inputs identified as DI point (O.S. 2.03.xx) 
Pull-Up Resistor Handling when Using Analog Inputs as 
Digital Inputs (O.S. 2.04.00 or higher) 
When the input is identified as a DI point in CARE (DI subtype 
AI), the internal pull-up resistor is disabled. 
10 Vdc 
Range 
Measurement error 
(without sensor tolerance) 
Pt1000 
NTC (20k ohms) 
-58 to –4 °F (-50 to –20 °C) 
 1.2 K 
 5.0 K 
-4 to 32 °F (-20 to 0 °C) 
 0.7 K 
 1.0 K 
32 to 86 °F (0 to 30 °C) 
 0.5 K 
 0.3 K 
86 to 158 °F (30 to 70 °C) 
 0.7 K 
 0.5 K 
158 to 212 °F (70 to 100 °C) 
 1.2 K 
 1.0 K 
212 to 266 °F (100 to 130 °C) 
 1.2 K 
 3.0 K 
266 to 302 °F (130 to 150 °C) 
 1.2 K 
 5.5 K 
ground 
Vi 
ground 
Vi 
200K ohm 
Fig. 77. Analog inputs identified as DI point (O.S. 2.04.00
or higher) 
Sensors and Transducers 
Passive sensors (NTC 20k ohms) 
Room temperature sensor RF20 
Inlet temperature sensor VF20A 
External temperature sensor AF20 
Active sensors (0 to 10 V): 
Duct Humidity Sensor H7011A1000 
Duct Humidity Sensor H7012A1009 
Active sensors (0 (4) to 20 mA): 
35 