Eaton Electrical Wireless Office Headset SC200 Manual De Usuario

Descargar
Página de 78
Installing the Battery Temperature Sensor (if batteries are fitted) 
 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
3-11
 
 
 
Terminate the Black/White wire at TEMP SENSOR (+) and the Black wire at 
TEMP SENSOR (-), as shown. 
To ensure reliable connections at the battery temperature sensor terminal blocks, torque the 
clamp-screws 0.4 – 0.6 Nm (3.5 – 5.3 lb-in). 
Use cable-ties (not supplied) and the provided cable-tie holes on the cable support bracket to tie 
down the battery temperature sensor cable. 
 
On APS3-061 power systems, there is a cable-tie hole on the bracket behind the battery 
cable clamp, to tie down the battery temperature sensor cable. 
Mounting the Battery Temperature Sensor 
The battery temperature sensor is designed to measure the average ambient temperature 
around the batteries.  It is important to mount the battery temperature sensor at a location 
that truly reflects the average ambient temperature of the batteries. 
Attaching the battery temperature sensor to the battery stand (centered and above the 
batteries) may provide the most reliable temperature reading. 
If possible, avoid: 
•  Placing the battery temperature sensor on top of battery cases. 
•  Attaching the battery temperature sensor to battery cables, terminals or interconnecting 
bars. 
•  Exposing the battery temperature sensor to direct sunlight and drafts from the air-
conditioning system or open windows. 
•  Running the battery temperature sensor cable along power or earth cables.