Johnson Controls M9220-GGX-3 Manual De Usuario

Descargar
Página de 12
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions
10
The master and slave(s) must spring return in the 
same direction.
Once tandem-operating actuators are mounted to 
a damper shaft, manual override is no longer an 
available function.
The feedback wire of the master (orange) is connected 
to the command wire(s) of the slave(s)(gray). As the 
master moves response to position commands, the 
master sets its feedback wire to 0 volts if moving 
counterclockwise, 5 volts if holding, or 10 volts if 
moving clockwise.
Each slave actuator must have its tandem selector 
switch (Figure 14) set on the slave setting. Its gray 
command wire must be connected the master’s orange 
feedback wire.
Position information, 0-10 (or 2-10) volts, is available 
on the slave actuator’s feedback wire (orange).
Auxiliary Switches (GGC Model Only)
The GGC models include two integral auxiliary 
switches with a switch adjuster accessible on either 
face of the actuator (as illustrated in Figure 2 and 
Figure 3). The nominal 
factory setting for Auxiliary 
Switch No. 1 is 11° closing, and the nominal factory 
setting for Auxiliary Switch No. 2 is 81° opening 
(relative to a 0 to 90° rotation range). See the Technical 
Specifications
 table for the auxiliary switch ratings.
The switch point of Auxiliary Switch No. 1 is fixed. The 
switch point of Auxiliary Switch No. 2 is independently 
and continuously adjustable from 25 to 95°. See 
Figure 16 and use the method in the following example 
for the most accurate positioning of Auxiliary Switch 
No. 2.
To change the switch point of Auxiliary Switch No. 2, 
proceed as follows:
1.
Position the actuator in the full spring return 
position.
Note: Auxiliary Switch No. 2 is factory set to trip 
when the actuator reaches the 81° position.
2.
Rotate the switch adjuster until it points to the 
desired switch point.
3.
Connect Auxiliary Switch No. 2 to a power source 
or an ohmmeter, and apply power to the actuator. 
The actuator moves to the fully open position and 
holds while power is applied.
4.
Observe the switch point. If required, repeat 
Steps 2 and 3.
Repairs and Replacement
A number of replacement parts are available; see 
Table 1 for more details. If the M9220-GGx-3 
Proportional Electric Spring Return Actuator fails to 
operate within its specifications, replace the unit. For a 
replacement electric actuator, contact the nearest 
Johnson Controls® representative.
!
WARNING: Risk of Electric Shock. 
Disconnect each of multiple power 
supplies before making electrical 
connections. More than one disconnect 
may be required to completely 
de-energize equipment. Contact with 
components carrying hazardous voltage 
can cause electric shock and may result 
in severe personal injury or death.
Figure 16: Switch Point Settings
A
FI
G
:s
w
p
n
t
Switch
Adjuster