Weil-McLain Gas Burner Hoja De Datos

Descargar
Página de 4
Weil-McLain 88 Water and Steam Boilers — Series 2 — 
For Gas, Light Oil, & Gas/Light Oil-Fired Burners
4
Part No. 550-142-029/0508
Notes for Table 3
Combustion Controls:
1. 
R7184P
 
Uses cadmium cell for flame detector to monitor oil burner flame, also furnishes intermittent ignition.
RM7897A, RM7897C
 
Uses ultraviolet electronic flame detector to monitor gas or oil burner flame and provides pre-purge programming.  “A” models 
provide intermittent pilot; “C” models provide interrupted pilot and RUN/TEST switch.  RM7897 provides same as above with 
post-purge.
RM7840L, E110/EPD170
 
Monitors the oil or gas burner flame, provides pre-purge and post-purge programming, provides switching necessary to allow 
firing rate motor to be driven to both low fire and high fire positions, prevents start-up if pre-ignition interlocks are open and 
has low fire start proving circuit.  In the event pre-ignition interlock circuit or running interlock circuit does not “prove”, system 
will lock out on safety. Ultraviolet sensitive electronic flame detector is standard with infrared detector available.
RM7800L, E110/EP160
 
Monitors the oil or gas burner flame with digital readout control system, provides pre-purge and post-purge programming, 
provides switching necessary to allow firing rate motor to be driven to both low fire and high fire position, prevents start-up 
if pre-ignition interlocks are open and has low fire start proving circuit.  In the event pre-ignition interlock circuit or running 
interlock circuit does not “prove”, system will lock out on safety.  Ultraviolet sensitive electronic flame detector is standard with 
infrared detector available.
Burner specifications and settings
  (continued)
  Flame safeguards
Table 3 
Flame Safeguards Provided with Listed Control Systems by Code
GAS BURNERS
Boiler 
Model 
Number
UL
FM
CSD-1
IRI
OO
LHO
LHL
MOD
OO
LHO
LHL
MOD
OO
LHO
LHL
MOD
OO
LHO
LHL
MOD
488R-588
RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897C RM7897C RM7897C RM7840L
688-988R
RM7897A RM7897A RM7897A
RM7897A RM7897A RM7897A
RM7897A RM7897A RM7897A
RM7897C RM7897C RM7840L
988-1388
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
1488-1888
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
LIGHT OIL BURNERS
Boiler 
Model 
Number
UL
FM
CSD-1
IRI
FALFS
LHO
LHL
MOD
FALFS
LHO
LHL
MOD
FALFS
LHO
LHL
MOD
FALFS
LHO
LHL
MOD
488R
R7184P R7184P R7184P R7184P R7184P R7184P R7184P R7184P RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7840L
488-588
R7184P R7184P R7184P R7184P R7184P R7184P R7184P R7184P RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7840L
688-1088R
R7184P R7184P R7184P
R7184P R7184P R7184P
RM7897A RM7897A RM7897A
RM7897A RM7897A RM7840L
1088-1288
RM7897A RM7897A RM7840L
RM7897A RM7897A RM7840L
RM7897A RM7897A RM7840L
RM7897A RM7897A RM7840L
1388-1888
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
COMBINATION GAS/OIL BURNERS
Boiler 
Model 
Number
UL
FM
CSD-1
IRI
OO/FALFS LHO
LHL
MOD OO/FALFS
LHO
LHL
MOD OO/FALFS
LHO
LHL
MOD OO/FALFS
LHO
LHL
MOD
488R-588
RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7897C RM7840L
688-988R
RM7897C RM7897C RM7897C
RM7897C RM7897C RM7897C
RM7897C RM7897C RM7897C
RM7897C RM7897C RM7840L
988-1288
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
RM7897C RM7897C RM7840L
1388-1888
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L
RM7840L RM7840L RM7840L