Pushbutton Controls
 The 
five pushbuttons (pictured below) on the 
DCM-2 customer interface panel are used for 
calibration.  When pressing a pushbutton, pressure 
should be maintained until the “ACKNOWLEDGE” 
LED lights; this confirms receipt of the pushbutton 
command.  See the Calibration section, beginning 
on page 25, for further explanation of the 
calibration procedures.  Pushbutton functions are 
as follows:
 CALIBRATE
 
 
A safety feature, this button must be 
pressed and held while pressing the 
pushbuttons described below to set the 
Position and Demand signal limits.   
CAUTION
Pressing the following buttons may change 
calibration and cause the drive to reposition.
 SET 
POS 
100% 
 
 
Press to set the desired 100% position for 
drive movement (this will correspond to a 
100% Demand signal).   
 
SET POS 0% 
 
 
Press to set the desired 0% position for 
drive movement (this will correspond to a 
0% Demand signal).
 
SET DEM 100%
 
 
Press to set the Demand input signal that 
corresponds to 100% Demand.
 
SET DEM 0% 
 
 
Press to set the Demand input signal that 
corresponds to 0% Demand. 
Status Indication LEDs
 
When the “STAT” LED is lit, the applicable status 
indication LED(s) (pictured below) will light to reveal 
the condition(s) as described below.  An alarm is 
also available at terminal E.  When the condition is 
corrected, the status will automatically reset.  Each 
status LED is described below, with a more detailed 
explanation of the function provided on page 21.  
 DEMAND
 
 
Loss of the Demand input signal.
 POSITION
 
 
The CPS Position signal to the DCM-2 is 
out of the calibrated range limits.  The lower 
limit is –5% and the upper limit is 105% of 
the calibrated range.  This LED may also 
indicate a CPS or internal wiring failure.
 TRQ/THRUST
 
 
This LED indicates that excessive torque 
is present (over 105% of the drive rating).  
This LED is functional only when the drive 
is equipped with optional torque sensing. 
 STALL
 
 
The drive is in a stall condition and stall 
protection has been activated.
 TEMP 
°F.
 
 
Drive’s internal temperature is outside of 
rating.
 FB 
OPEN
 
 
External position Feedback signal is 
enabled, but not wired to an external load 
or the wiring has failed between the drive 
and the monitoring device.
 STOP/LIMIT
 
 
Handswitch is in “STOP” position or the 
drive is at a limit and is not in balance. 
Status
Indication
LEDs
Pushbutton
Controls
DCM-2 LOCAL INTERFACE
 
Operation
ACKNOWLEDGE
CALIBRATE
SET POS
100%
SET DEM
100%
SET DEM
0%
SET POS
0%
R
FWD
REV
STAT
PWR
POSITION
DEMAND
TQ/THRST
STALL
FB OPEN
STOP/LIMIT
TEMP F
POSITION
DEMAND
TRQ/THRUST
STALL
FB OPEN
STOP/LIMIT
TEMP F
R
FWD
REV
STAT
PWR
CALIBRATE
SET POS
100%
SET DEM
100%
SET DEM
0%
SET POS
0%
ACKNOWLEDGE