Short-stroke Operation 
(Reducing Full Travel)
 
Typically, it is best to use the full 100% travel 
of the drive in response to the 0–100% Demand 
input signal.  
 
In certain applications, as a last resort, it may 
become necessary to reduce the full travel of the 
drive.  In these applications, the DCM-2 can be 
calibrated to accommodate reduced stroke.  The 
recommended minimum full travel is 60%, although 
it is advisable to make the range as close to 100% 
as possible for the highest position resolution 
attainable with the CPS and to avoid possible 
reduction in torque.
 
Reducing the full travel is referred to as 
“short-stroking” the drive.  This can be easily 
accomplished by using a HART communication 
device.  
 
First, navigate to the Configuration menu.  
Select the General Setup submenu.  Select the 
Travel parameter.  Reduce the stroke by entering 
a percentage of full travel (not less than 60%) of 
the maximum travel of the drive.