EUROLIGHT LD6230 Installation Instructions
The BEHRINGER EUROLIGHT LD6230 Dimmer Pack was developed to meet 
the highest demands of light engineering. Its wide-ranging functions 
make it an all-purpose workhorse for various commercial applications 
(TV studios, theatre or live events). 
The EUROLIGHT LD6230 has all the important features needed to control your 
lighting equipment, yet its controls are clearly arranged and simple to use. 
You can select between digital DMX or analog control. You get trouble-free 
operation with the extensive LEDs used for signal error detection.
Important Information
◊ 
Installation as well as initial operation must be performed by qualified 
personnel. Always assure that your LD6230 is completely disconnected 
from the mains before removing the casing cover.
◊ 
The LD6230 was designed for indoor use only.
◊ 
Please keep in mind that sudden temperature changes (e.g. bringing 
your equipment from colder environments into warmer environments) 
may cause condensation on electronic components, leading to possible 
equipment damage and physical harm to the operator.
◊ 
Please adhere to all applicable national safety standards 
during installation.
◊ 
Please read the installation instructions and the enclosed user’s 
manual in their entirety to familiarize yourself with the LD6230 
and all of its functions. Please follow all instructions and store both 
the installation instructions and the manual in a safe place for 
future reference.
◊ 
Please assure that your EUROLIGHT is sufficiently cooled and that it is 
not placed near heat sources that could cause overheating.
◊ 
If you want to run your EUROLIGHT on mains voltage other than 
factory-specified voltage, contact the nearest BEHRINGER service center.
◊ 
To effectively limit harmonic currents and avoid voltage fluctuations that 
could affect other electrical appliances, connect this equipment to an AC 
outlet that complies with all applicable technical standards. In all other 
cases, contact your local power supply provider for advice prior to usage.
Mains/Illuminant
 
Connectors 
To facilitate additional flexibility, your dimmer pack has a connector terminal 
strip. Cable bushings for connecting to the mains and your illuminants are 
located in the back. Flexibility is further enhanced with the option to retrofit a 
CEE connector and a 16-pin HARTING connector. 
Both fixed and mobile installations require compliance with IEC 61010-1:2001 
(EN 6110-1:2001). In particular, a 3-phase
 
separator (pursuant IEC60947-1 and 
IEC60947-3) needs to be included in the installation. This separator needs to be 
labeled according to IEC 60417-50008 and IEC 0417-5007.
To assure compliance with 
Directive 89/336/EEC
only use specified upstream line 
filters with your EUROLIGHT. Using it without line filters specified by BEHRINGER 
may lead to electromagnetic interference. More detailed information on this 
subject can be found at behringer.com.
Safety and Initial Operation
As soon as you connect your LD6230 to the mains, internal controls are activated. 
The six 
automated fuses (circuit breakers) 
can all handle 10 A and serve as 
overload protection for the connected equipment.
◊ 
Please keep in mind that activating circuit breakers 1, 2, 3, 4, 5 or 6 also 
means that the respective channels can conduct voltage.
Electronic controls are additionally protected with triple high-sensitivity fuses 
located on the main board. 
◊ 
Defective fuses must be replaced with fuses with identical rating!
The LD6230 is a Class I device in which a low-Ohm protective ground wire is an 
integral part of its safety design.
During the installation, make sure that a low-Ohm protective conductor (< 0,1 Ohm) 
exists between all bare metal parts and the grounding on the main connector.
Output Channels
Phase
CH 1*
CH 2
CH 3*
CH 4
CH 5*
CH 6
L1
X
X
L2
X
X
L3
X
X
* Activation of control electronics and respective output channel
Connector Terminal Strip
The connector terminal strip of your LD6230 is laid out for cables with diameters 
between 0.326 mm
2
 (AWG 22) and 4 mm
2
 (AWG 12). When using flexible access 
lines, cable end contacts corresponding to manufacturer specifications have to be 
used. To assure good contact, skin the cable endings between 9 - 13 mm.
During the installation, all applicable national standards need to be adhered to.
(2)
(2)
(1)
(3)
(4)
Illustration: LD6230 connector terminal strip
When your LD6230 leaves the assembly plant, all incoming and outgoing 
neutral conductor connectors  
(3)
  are bridged. The incoming phases L1/L1, 
L2/L2 and L3/L3  
(1) 
 are always connected to one another in pairs and 
switched to the overload protection of the channels 1 to 6. They protect output 
connectors E1 to E6  
(4)
. Each of the channels can handle currents of maximum 
10 Amperes. The green-yellow conductors  
(2) 
 (PE) may only be used as 
protective conductors.
The lowest cable gauge between L1 and L3, incoming neutral conductor (N) 
and protective earth (PE) is 4 mm
2
 (AWG 12). For outgoing channels E1 to E6, 
use cables with gauges corresponding to the loads used (2.5 mm
2
 (AWG 14) 
or 1.5 mm
2
 (AWG 16)).
◊ 
Output assessment [A] Nominal cross section [mm²] (EU)
AWG (USA)
6-10
1.5
16
13-16
2.5
14
18-25
4
12
During the installation, please adhere to all manufacturer instructions. 
Regardless from mains supply voltage, the maximum output current of 
the EUROLIGHT LD6230 is 10 A per dimmer circle.