Explosion Hazard. Can 
Cause Severe Injury, Death 
or Property Damage.
Use this product only in systems with a pressure relief 
valve.
Wiring the AquaSmart Control
Consult the appliance wiring diagrams to check the 
manufacturer’s specifi cations.
Refer to Figure 12 through Figure 17 for some 
typical wiring diagrams.
Verify the wires are still labeled correctly and make 
connections to the appropriate terminals on the 
control wiring terminal strip.
Provide disconnect means and overload protection 
as required on power supply.
Connect control conduit bracket to earth ground 
using the supplied grounding screw.
B1 terminal is a 1/4 in. tab terminal (quick connect).
Figure 11 - TR, B2, & Vent Damper Connections
Water Flow Symbols Key (Figures 12 through 17)
Z
 -  Air Vent
 -  Air Separator
 -  Expansion Tank
 -  Isolation Valve
 -  Pressure Regulator
 -  Zone Valve
 -  Check Valve
 -  Circulator
Some Thermostats Are 
Polarity Sensitive
Reversed polarity could cause erratic cycling of the 
boiler control.
Connect the red thermostat wire (from the RH or R 
terminal of the thermostat) to the T
R
 terminal on the 
control.
Connect the white thermostat wire (from the W 
terminal of the thermostat) to the T
W
 terminal on the 
control.
y
y
7600B only:  TERMINALS TR (Z or 
hot) and B2 (TV or ground) offer a 
24-volt supply for operating other 24 VAC equipment on 
the boiler.  IMPORTANT: TO PREVENT DAMAGE TO 
THE CONTROL, DO NOT OVERLOAD THE 
TRANSFORMER.
  The AquaSmart is equipped with a 
30VA transformer.  Make sure that the total load, 
including the burner circuit and TR & B2 connections do 
not exceed 30VA. See Figure 11.
How to calculate VA - Add all AMP ratings of 24VAC 
components in this circuit and multiply sum by 24 volts. 
(Example: .4 + .4 + .2 + .2 = 1.2A x 24V = 28.8 VA)
When powering multiple circulators 
from the C1 and C2 terminals, take 
extra care not to exceed the output’s reading.  If the sum 
of the full load amps of all the circulators exceeds the 
output’s rating, use the C1 and C2 terminals to power the 
coil of a multiple-pole contactor; the contacts of which can 
be wired to switch L1 to each circulator.
Observe proper polarity when wiring 
L1 and L2.  If polarity is reversed, a 
call for heat on the ZR input may not be recognized.
TR
B2
To wire a vent damper to the 7600B, 
fi rst remove jumper plug from 6-
position receptacle and then connect 6-pin connector of 
the vent damper to the receptacle.  See Figure 11.  Once 
the 7600B is operated with a vent damper, it will not 
function without one (even if the jumper plug is replaced).
6-Position Vent 