Programmable Electronic Digital Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
FAILURE TO  READ  AND  FOLLOW  ALL  INSTRUCTIONS  CAREFULLY 
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
 
 DESCRIPTION
•  Temperature override until next program period
•  Manual program override (HOLD temperature)
•  Temporary HOLD
•  °F/°C convertibility
•  Temperature range 45° to 90°F
•  RC, RH, C, W, Y, G , O and B terminals
•  Optional C terminal (Dual Power option)
•  B and O terminals for single stage heat pumps (no auxiliary
heat) or damper operation
•  Program storage in case of power loss
•  2 “AA” Energizer
®
alkaline batteries included
Operator:  Save these instructions for future use!
Your  new  White-Rodgers  7-Day  Digital Thermostat  uses  the
technology  of  a  solid-state  microcomputer  to  provide  precise
time/temperature control. This thermostat offers you the flexibility
to design heating and cooling programs that fit your needs.
Features:
•  Separate program for each day of the week with four separate
time/temperature periods per day
•  Simultaneous heat and cool program storage
•  Preprogrammed temperature control
•  Backlit display
•  LCD continuously displays setpoint, and alternately displays
time and room temperature
 
 PRECAUTIONS
This thermostat is intended for use with a low voltage system;
do not use this thermostat with a line voltage system. If in doubt
about whether your wiring is millivolt, line, or low voltage, have it
inspected by a qualified heating and air conditioning contractor
or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
!
CAUTION
To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.
!
WARNING
Do  not  use  on  circuits  exceeding  specified  voltage. 
Higher voltage will damage control and could cause 
shock or fire hazard.
Do  not  short  out  terminals  on  gas  valve  or  primary 
control to test. Short or incorrect wiring will damage 
thermostat  and  could  cause  personal  injury  and/or 
property damage.
Thermostat installation and all components of the system 
shall conform to Class II circuits per the NEC code.
 
 SPECIFICATIONS
ELECTRICAL DATA
Electrical Rating: 
8 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
 
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range: 
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-4°F to 149°F
APPLICATIONS
For use with:
•  Standard heat/cool or heat only systems
•  Electric heat systems
•  Gas or oil fired systems
•  Gas systems with intermittent ignition devices (I.I.D.)
 and/or vent dampers
•  Hydronic (hot water or steam) systems
•  Single-stage heat pump systems (no auxiliary heat)
•  Millivolt systems
DO NOT USE WITH:
•  Multi-stage systems
•  Systems exceeding 30 VAC and 1.5 amps
•  3-wire zoned hydronic heating systems
PART NO. 37-6763B
Replaces 37-6763A
1006