White Rodgers 1F95-1271 Guía De Operación

Descargar
Página de 8
4
CONFIGURATION MENU
Non-
Displayed
Press  
 or 
Program- Program-
Press
(Factory
to select from
mable
mable
Button
Default)
 listed options
Comments
1
1
MS 2
HP 1, HP 2, SS 1
Selects Multi-Stage (MS 2, No Heat Pump), Heat Pump 1
(HP 1, 1 compressor), Heat Pump 2 (HP 2, 2 compressor
or 2 speed compressor), or Single Stage.
2
2
(GAS)
ELE
GAS setting: furnace controls blower.
ELE setting: thermostat controls blower.
3
3
Days (7)
5, 0
Selects programming option.
4
*  NA
PS (4)
2
Selects programming steps per day.
5
4
Cool Off
Cool Off  Heat (Emer), Selects system switch configuration for Heat and Cool with
Heat Auto
Off  Heat, Cool Off
Auto changeover, Heat & Cool, Heat Only or Cool Only.
6
*  NA
E (On)
OFF
Selects Energy Management Recovery on or off.
7
5
Cr Heat (FA)
SL
Selects Heat cycle rate Fast (FA) or Slow (SL).
8
6
Cr Cool (FA)
SL
Selects Cool cycle rate Fast (FA) or Slow (SL).
9
7
Cr Emer (FA)
SL
If HP 1 or HP 2 is selected for item #1, selects Emer cycle
rate.
10
8
CL (OFF)
On
Selects Compressor lockout ON or OFF.
11
9
dL (On)
OFF
Selects display light on or off.
12
10
0
1, 2, 3, 4 HI
Selects temperature display adjustment 1, 2, 3 or 4 degrees
(Room temp)
1, 2, 3, 4 LO
high or low.
13
11
°F
°C
Selects Fahrenheit or Celsius temperature display.
14
12
b (On)
OFF
Selects beeper on or off.
15
13
Heat (99)
62-99
Selects highest Heat setpoint temperature.
Can select 62° to 99°F.
16
14
Cool (45)
45-82
Selects lowest Cool setpoint temperature.
Can select 45° to 82°F.
17
15
 Keypad
L, P
Selects keypad lockout full or partial to be set.
lockout (L)
Temperature Limit
Activates temperature limit ranges.
18
16
 Keypad
On
Selects keypad lockout on or off.
lockout (OFF)
000
000 to 999
Selects keypad lockout combination number if  lockout is on.
000 is not a valid selection.
19
17
FA Heat (On)
OFF
If HP or MS selected in item 1, selects Heat Fast second
stage On or Off.
20
18
FA Cool (On)
OFF
If HP or MS selected in item 1, selects Cool Fast second
stage On or Off.
21
19
000 Change
On
Select change filter alert time period.
Filter (OFF)
200 hours
25 to 1975 hours
When set ON, selects time in 25 hour increments.
22
20
Change
On
Selects change humidifier pad alert time period
Humidifier
(OFF)
100 hours
25 to 1975 hours
When set ON, selects time in 25 hour increments.
INSTALLER/CONFIGURATION MENU
To enter the menu: Press the 
Menu button. Press and hold for 5 seconds the Installer Config button. This displays menu
item #1 in the table below. Press 
 to advance to the next menu item or 
 to return to a previous menu item. Press 
 or 
to change a menu item.
1) This control can be configured for:
MS2 – Multi-Stage System (no heat pump)
HP1 – Heat Pump with one stage of  compressor
HP2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup
SS1 – Single Stage System
2) GAS or Electric (ELE) fan operation. If  the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if  the heating system energizes the fan on a
call for heat. 
Note: Resetting the thermostat switches
the option to ELE.
3) This control can be configured for 7 independent day or
5/1/1 day programming or non-programmable mode. The
display indicates "
7 Days" as default. The programs per
week can be toggled to "
5 Days" or "0 Days" by pressing
the 
 or 
 keys. A selection of  0 Days for non-program-
mable will eliminate the need for EMR, and that step
in the menu will be skipped.
4)
Programmable Periods – This control can be configured
for 4 or 2 programmable periods per day. The display
indicates "
4 PS" in the display as default. The program-
mable periods can be toggled by pressing the 
 or 
keys.
Menu
Reference
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
* Not Applicable