Conventional Method:
You may connect both the strobe and the horn directly from a source of rated power without the use of a control module.  However, the horns and strobe
lights will NOT be synchronized.  Place switches and up on the GEC3-12 (Fig.1) to power both the audible and visible from a single pair of power
wires. If you wish to power the horn and strobe from independent sources of power, place switches and down on the GEC3-12 and connect power to
the appropriate terminals.
CAUTION: When using only a single power source to energize the strobe and 
horn (switches 1 and 2 up), the in/out wiring must be under the S+ 
and S- terminals only.  Failure to do so may result in damage to
your signal.  For the horn only (GEH12) and strobe only (GES3-12), 
only the top three terminals are to be used.
NOTE: INSTALLATION IN CANADA - All Canadian installations should be in    
accordance with the Canadian Standard for the Installation of Fire 
Alarm Systems- CAN/ULC S524-01 the Canadian Electrical Code, Part 1.
MAX. WIRE        
(PANEL VOLTAGE-APPLIANCE MIN. VOLT) X WIRE CONDUCTIVITY
 DISTANCE   =
  (IN FEET)                            
TOTAL CURRENT DRAW
WIRE
CONDUCTIVITY
18AWG
60
16AWG
95
14AWG
153
12AWG
244
Includes wire to and from appliance.  CAUTION: Applies only to
regulated supplies.  Assumes all appliances are at the end of
wire run (worst case).
Grip both
sides of bezel
and pull in a
downward
and outward
motion.
3
Fig. 1
Regulated 12V Maximum
Candela
 DC(mA) Operating Current
15
163
30
212
60
331
75
436
Strobe Current Ratings