Conventional Method:
You may connect both the strobe and the horn directly from a source of rated power without the use of a control module. However, the horns and strobe
lights will NOT be synchronized. Place switches 1 and 2 up on the GEC3-12 (Fig.1) to power both the audible and visible from a single pair of power
wires. If you wish to power the horn and strobe from independent sources of power, place switches 1 and 2 down on the GEC3-12 and connect power to
the appropriate terminals.
lights will NOT be synchronized. Place switches 1 and 2 up on the GEC3-12 (Fig.1) to power both the audible and visible from a single pair of power
wires. If you wish to power the horn and strobe from independent sources of power, place switches 1 and 2 down on the GEC3-12 and connect power to
the appropriate terminals.
CAUTION: When using only a single power source to energize the strobe and
horn (switches 1 and 2 up), the in/out wiring must be under the S+
and S- terminals only. Failure to do so may result in damage to
your signal. For the horn only (GEH12) and strobe only (GES3-12),
only the top three terminals are to be used.
and S- terminals only. Failure to do so may result in damage to
your signal. For the horn only (GEH12) and strobe only (GES3-12),
only the top three terminals are to be used.
NOTE: INSTALLATION IN CANADA - All Canadian installations should be in
accordance with the Canadian Standard for the Installation of Fire
Alarm Systems- CAN/ULC S524-01 the Canadian Electrical Code, Part 1.
MAX. WIRE
(PANEL VOLTAGE-APPLIANCE MIN. VOLT) X WIRE CONDUCTIVITY
DISTANCE =
(IN FEET)
(IN FEET)
TOTAL CURRENT DRAW
WIRE
CONDUCTIVITY
18AWG
60
16AWG
95
14AWG
153
12AWG
244
Includes wire to and from appliance. CAUTION: Applies only to
regulated supplies. Assumes all appliances are at the end of
wire run (worst case).
regulated supplies. Assumes all appliances are at the end of
wire run (worst case).
Grip both
sides of bezel
and pull in a
downward
and outward
motion.
sides of bezel
and pull in a
downward
and outward
motion.
3
Fig. 1
Regulated 12V Maximum
Candela
DC(mA) Operating Current
15
163
30
212
60
331
75
436
Strobe Current Ratings