Instruction Manual – Model CF500/CF800 Oil Burner
  Z dimension
• Should be set per these instructions (see page 7). The acorn
nut (
Figure 6
, item 
c
, page 7) should never be loosened
once the 
dimension is initially set.
  Initial head position
• The indicator plate assembly markings correspond to head
position settings.
• Loosen the fastener (
Figure 6
, item 
d
, page 7) and slide
the indicator plate until the number on the plate corre-
sponds to the initial head setting given in 
Table 4
 for the
desired firing rate.
• When the head position has been set, tighten the fastener
and spline nut.
  Initial air settings
• Loosen the air band and shutter, and adjust to the settings
for the applicable firing rate shown in 
Table 5
.
• These initial settings should be adequate for starting the
burner. Once the burner is in operation, the air settings will
Table 4 – Initial indicator adjustment plate settings
(head position)
Prepare the burner for start-up
Start-up checklist
   –  
Verify the following
before attempting to start burner.
❏ Combustion air supply and venting have been inspected
and verified to be free of obstructions and installed in
accordance with all applicable codes.
❏ Oil nozzle has been selected correctly and securely installed
in the nozzle adapter.
❏ Fuel unit by-pass plug 
has not
 been installed for one-pipe
oil system.
By-pass plug 
has been
 installed for two-pipe oil system.
❏ Fuel connection to nozzle line assembly is secure.
❏ Dimension has been set per this instruction manual.
❏ Fuel supply line is correctly installed, the oil tank is
sufficiently filled, and shut-off valves are open.
❏ Burner is securely mounted in appliance, with pressure
firing plate and gasket installed for pressurized chamber
application.
❏ Appliance has been filled with water (boilers) and controls
have been operationally checked.
❏ Burner has been installed in accordance with appliance
manufacturer’s instructions (when available).
❏ Also refer to appliance manufacturer’s instructions (when
available) for start-up procedures.
Table 5 – Initial air settings
Rate
GPH
Approximate air settings
CF500
CF800
Tube A
Tube  B
Shutter
Band
Shutter
Band
Shutter
Band
1.75
1
0
--
--
--
--
2.25
2
0
--
--
--
--
3.00
10
1
1
0
--
--
3.50
10
2
3
0
--
--
4.00
10
3
4
0
--
--
5.00
10
5
9
0
8
2
5.50
10
10
9
5
9
4
6.00
--
--
10
3
10
3
7.00
--
--
10
8
10
5
8.00
--
--
--
--
10
10
be adjusted for best performance as discussed later in this
manual.
• Follow the procedures given later in this manual for fine-
tuning the air settings.
  Set appliance limit controls
• Set the appliance limit controls in accordance with the
appliance manufacturer's recommendations.
  Prepare the fuel unit for air venting
• To vent air from one-pipe oil systems, attach a clear hose to
the vent plug on the fuel unit. Provide a container to catch
the oil. Loosen the vent plug.
• Vent the air as described under 
Start the burner
, page 13,
when using the R7184 control.
Rate
GPH
Approximate head settings
CF500
CF800
Tube A
Tube  B
1.75
0
--
--
2.25
0
3.00
4
0
--
3.50
5
1
--
4.00
5
2
--
5.00
6
4
3
5.50
6
4
4
6.00
--
4
4
7.00
--
6
5
8.00
--
--
6