Detector Settings
System Sensitivity
The UV tube count rate generated by different fires at the same distance is unpredictable. Generally if a fire
doubles in size, the tube response is increased by about 60 percent. The UVU-140-A & UVU-140-AR detectors
have selectable sensitivity settings which allow for various applications regardless of the severity of the hazard
and the action required if a fire occurs. The system can be adjusted to various sensitivity levels by setting the
detectors to respond at a pre-determined detector count rate. The count rate is dependent upon the intensity of the
ultraviolet radiation reaching the detector, which in turn depends on the type of fuel, temperature, flame size,
distance from the detector and concentration of UV absorbing vapours present. Setting the UVU-140-A & UVU-
140-AR detectors to respond to a low count rate results in high system sensitivity. Adjustments are made by
setting the DIP switch on the bottom of the internal module. The factory settings are 5 second time delay at 24
counts per second (cps), the fire relay is de-energized and latching
.
Table 1 - Detector Sensitivity Settings
SYSTEM  SENSITIVITY SETTINGS
Switch 1
Switch 2
  8 Counts (cps)
ON
ON
16 Counts (cps)
ON
OFF
24 Counts (cps)
OFF
ON
32 Counts (cps)
OFF
OFF
System Time Delay
Time delay can be set via dip switches located on the bottom of the electronics module . See Figure 7.
Table 2 - Alarm Response Delay Settings
SYSTEM  TIM E DELAY SETTINGS
Switch 3
Switch 4
3 Seconds
ON
ON
4 Seconds
ON
OFF
5 Seconds
OFF
ON
7 Seconds
OFF
OFF
Coil and Relay Settings
The DIP switch is located in the JBR-T assembly.