Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
External Communication—Building Management Systems, Liebert SiteScan
®
99
Liebert
®
 iCOM
®
6.0
E
XTERNAL
 C
OMMUNICATION
—B
UILDING
 M
ANAGEMENT
 S
YSTEMS
, L
IEBERT
 
S
ITE
S
CAN®
Liebert iCOM is capable of communicating with external monitoring systems, such as Building 
Management Systems (BMS), Network Monitoring Systems (NMS), Liebert's SiteScan
®
 Web and 
others.
Each Liebert iCOM-controlled cooling unit is equipped with Liebert IntelliSlot
®
 plug-in slots for use 
with optional communication cards. Two hot-swappable cards are available to provide remote 
communication to the Liebert iCOM.
The Liebert IntelliSlot
 IS-UNITY-DP communication card monitors and manages a range of 
operating parameters, alarms and notifications. Unity cards deliver:
• Emerson Protocol for Trellis
, Liebert SiteScan
 and Liebert Nform
®
• Embedded LIFE
 Technology for Remote Service Delivery
• SNMP (v1/v2c/v3) for Network Management Systems
• HTTP/HTTPS for Web page viewing
• SMTP for e-mail
• SMS for mobile messaging
• Modbus RTU-Modbus Remote Terminal Unit (RTU) communication protocol for Building 
Management Systems over a RS-485 serial network (also called Modbus RTU RS-485)
• Modbus TCP-Modbus Transmission Control Protocol for Building Management Systems over an 
Internet or LAN
• BACnet IP—BACnet over Internet Protocol for Building Management Systems over the Internet 
or a LAN
• BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communication protocol for 
Building Management Systems over an RS-485 serial network (also called BACnet MSTP RS-485)
The Liebert IntelliSlot Unity platform supports communication with up to two third-party protocols 
simultaneously. Velocity V4 monitoring protocol is required to ensure monitoring connectivity with 
the Liebert IntelliSlot IS-UNITY-DP. Velocity V4 protocol is standard in Liebert iCOM software 
version PA1.04.033 and later. 
Another communication option is the Liebert IntelliSlot SiteLink-E
®
 CARD (IS-485EXI), which 
provides ground fault isolated connection to a Liebert SiteLink-E for monitoring and management. 
The IS-485EXI is compatible with all Liebert iCOM software versions. See the Liebert Web site for 
the latest supported protocols, monitoring reference information and SNMP MIBs: 
6.1
Building Management Failover Features
A Monitoring Timeout/Handshake can be used with a building management system to verify 
communication between the Liebert iCOM and the BMS. The handshake or communication test is 
performed through a timer in the Liebert iCOM. If communication is OK, the BMS will update the 
timer periodically. If the BMS fails to perform a handshake within the specified period (e.g., 
monitoring panel failed) the Liebert iCOM will generate a BMS TIMEOUT event.