Emerson Liebert iCOM Manual De Usuario
Service Menu Parameters
123
Liebert
®
iCOM
®
S110 Supply Limit Enabled/Setpoint—Chilled water units may be set up with the supply air
sensor to maintain a minimum air temperature under a raised floor to help prevent condensation. In
order to avoid supply temperatures that are too low, the Supply Limit can influence the opening of
three-point or analog actuators or the output of analog valves. The control compares the deviation
from the return air setpoint and the supply limit setpoint, and calculates the output to the actuator
from the smaller deviation.
S111 Heater Deadband—Changes the amount of deviation below the temperature setpoint that the
S111 Heater Deadband—Changes the amount of deviation below the temperature setpoint that the
heaters will cycle On and Off. This value is added to the heating side of the normal temperature
deadband.
Figure 107
Setpoints screen, page 2 of 10
S113 Enable Temp Compensation—Temperature compensation allows for a second or third sensor
to be used that will influence the unit’s cooling or heating. Three selectable values are available:
Return, Supply, and Ret + Sup (Return + Supply). See Temperature Compensation on page 60
for more information on temperature compensation.
S114 Return Compensation Setpoint—The temperature setpoint where compensation begins to
S114 Return Compensation Setpoint—The temperature setpoint where compensation begins to
operate by increasing the supply air setpoint.
S115 Return Compensation Band/Value—The return compensation band / value will determine
S115 Return Compensation Band/Value—The return compensation band / value will determine
how quickly the cooling capacity is adjusted as the return temperature drops below the return
compensation setpoint.
S116 Supply Compensation Value—The Supply Compensation value determines how much the
S116 Supply Compensation Value—The Supply Compensation value determines how much the
supply temperature setpoint will be reduced when the units fan speed is at 100% and the cold aisle is
not able to maintain temperature setpoint.
Any modifications to the supply temperature setpoint will be shown at the temperature setpoint on
Any modifications to the supply temperature setpoint will be shown at the temperature setpoint on
parameter S103 as the actual active control point.
S118 Comp Cap Filter at 0-100%—Controls the rate of change during comp load changes to avoid
S118 Comp Cap Filter at 0-100%—Controls the rate of change during comp load changes to avoid
overshoots. The filter value depends on the current control deviation from the setpoint.
On the setpoint (at 0%), it’s typically set lower (slow), and at the end of the P-band (at 100%) it’s
On the setpoint (at 0%), it’s typically set lower (slow), and at the end of the P-band (at 100%) it’s
typically set higher (faster). The value is given in % control output change per second.
S119 Capacity Transition Filter—This parameter should only be adjusted by a factory-service
S119 Capacity Transition Filter—This parameter should only be adjusted by a factory-service
trained technician. The transition capacity filter controls how quickly the capacity changes between
different modes of operation.
This filter helps with the transition to avoid overshoot.
This filter helps with the transition to avoid overshoot.