Liebert iCOM Display Components and Functions
Liebert
®
 iCOM
®
4
2.1
Control Interface—Large Display
The Liebert iCOM automatically opens to the Unit View Status Menu when the cooling unit is 
started. This view will display “Unit 1” in the upper right corner of the screen.
Figure 3
Unit view status menu
When no button on the Liebert iCOM control has been pressed for a short period, the display 
backlight turns Off. Pressing any key will reactivate the screen and display the status menu of the 
last cooling unit viewed.
The status menu will show the cooling unit’s operational mode, including information such as return 
air temperature and humidity readings, temperature and humidity setpoints and any active alarms.
Symbols on the Liebert iCOM screens, shown in Figure 4, denote the operating modes. 
Figure 4
Liebert iCOM default screen symbols
Liebert iCOM 
Navigation 
Guide
Immediately 
Preceding 
Status
Current 
Status
Current Fan 
Speed 
Percentage
Current 
Cooling
Next Scheduled 
Maintenance 
Date
Unit 
Identification
Setpoints
(Return Temperature, Humidity 
and Supply Temperature)
Actual
Return 
Temperature, 
Humidity and 
Supply 
Temperature
Freecooling
Hot Water
Fan
Cooling
Maintenance
Electric Heat
Dehumidification
Humidification