Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Service Menu Parameters
181
Liebert
®
 iCOM
®
Figure 174
Remote sensors, page 2 of 2
SB15 Auxiliary Air Temperature- enables or disables the wireless sensor connection.
SB16 Auxiliary Proxy Status—displays the proxy server communication status. Status's include 
'initializing', 'active', 'inactive or lost.
• Initializing: Displayed immediately after the start of the Liebert iCOM process responsible for 
tracking the communication state, or immediately after the Auxiliary Air Temperature value is 
enabled.
• Active: Displayed during normal operation.
• Inactive: Displayed when iCOM becomes disconnected from the proxy.
• Lost: Displayed when the Liebert iCOM is disconnected from the proxy and the Heartbeat Event 
Timer has elapsed.
SB17 AP Heartbeat / Event Timer—the left parameter is a timer that resets every time iCOM 
receives an information packet is from the proxy. If iCOM does not receive a packet within the time 
specified, the Auxiliary Proxy Status will show lost and the Event timer (right hand value) will start 
counting down. If iCOM does not receive a packet before the event timer has reached zero, an AUX 
SENSOR DISCONNECT event will become active. 
SB18 Raw Auxiliary Air Temperature—The air temperature reading reported by the wireless 
proxy in degrees Fahrenheit or degrees Celsius. 
SB19 Act Auxiliary Air Temperature—The remote temperature reading after wireless sensors is 
weighted with hard-wired sensors. The parameter reports in either degrees Fahrenheit or degrees 
Celsius.
SB20 Auxiliary Weighting in TW AVG—Represents the weight applied to the Actual Auxiliary Air 
Temperature, relative to the wired sensor value from each unit reported to the master. The range is 0 
to 100% with a default of 0. The parameter will be hidden unless Teamwork is based on is set to 
Average.