Operation
21
Liebert
®
 iCOM
®
Minimum Fan Speed
Depending on the product control design, there may be an internal minimum speed, as defined by 
that specific product operation. Minimum fan speeds are defined below.
• Direct expansion units with pressure transducers 70%
• Chilled water units 60% (available option to 25%)
• Direct expansion units with low-pressure switches limited to 80%.
• Direct expansion units with standard scroll or 2-step semi-hermetic compressor(s) limited to 
100%.
Contact your local Emerson dealer for more information if fan speed minimum settings must be 
lowered from the values above.
Additional fan speed configuration parameters include a fan speed filter and fan speed reposition 
delay timer. These parameters allow fine tuning the fan speed control and, except for setting to 
Manual, are applicable to any other operation mode set in the VSD fan speed setting.
• The fan speed filter allows the fan to respond at a different rate depending on the location of the 
control point within the proportional band.
Example: When the controlled temperature is near the setpoint or at conditions where the 
proportional band output is decreasing and approaching 0%, the fan speed change rates are 
proportionally decreased to avoid overshooting the controlled temperature. However, when the 
temperature rises above the setpoint or at conditions where the proportional band output is 
increasing, the fan speed change rates are proportionally increased.
• The fan speed reposition delay timer setting in the Liebert iCOM menu may be changed to 
improve the fan operation stability if it is oscillating. The delay timer holds back the fan output 
change until each delay period is reached if fan speed is decreasing. If fan speed is increasing, 
then the delay timer has no effect.
Fluid or Air Economizer with Variable Fan Speed Fans
An option in Service Menus > Setpoints > FC / AirEco Ramp Up w/CFC, allows the fan to ramp with 
the economizer. The default value is No, allowing the fan ramp independently of free-cooling. When 
set to Yes, the control will compare the call for fan to the free-cooling request. This will provide the 
most capacity from the Liebert Air Economizer and will help in holding off the mechanical cooling 
(second stage). When the economizer is not available, the fan will ramp based on the fan control 
sensor deviation from setpoint.
NOTE
• The fan speed lower and upper limit settings are set at the factory.
• The standard fan speed control will be overridden during a call for Dehumidification if the 
function is enabled. When there is a call for dehumidification, the fan speed will change to 
the VSD Setpoint Dehum parameter found in the Service Menu>Setpoints. This routine may 
be disabled in Service Menus>Options setup line S419.
• The standard fan speed control will be overridden during a call for humidification or reheat. 
During a call for humidification or reheat, the fan speed will change to a higher speed, 
which is set at the factory to eliminate the possibility of condensation or damage to the unit.
NOTE
This feature is overridden in Manual fan control. Fan control must be in a decoupled mode.