Emerson Liebert iCOM Manual De Usuario
Operation
65
Liebert
®
iCOM
®
3.9.2 Static Pressure Control
Static pressure control normally refers to the control of a variable air flow device that will maintain a
differential static pressure between two points. The two points of measurement are typically a
point(s) below the raised floor in comparison to a point(s) above the raised floor, also known as ESP
(External Static Pressure). There are other static pressure points within the data center that have
also been used for control like the pressure differential between the inlet of a server rack as it
compares to the outlet of a server rack in a containment application. No matter where the differential
pressure is measured for control, the objective behind the control is to achieve the same result. Since
static pressure measures the potential to flow air from the area of a higher pressure to a lower
pressure, the result static pressure is trying to achieve is air flow.
The control method of static pressure is to define a setpoint in either inches of water column or in
The control method of static pressure is to define a setpoint in either inches of water column or in
Pascal’s that a controller will use to compare the actual differential pressure reading from either a
single pressure sensor or multiple pressure sensors. The actual reading from the sensor is then
compared to the static pressure setpoint and the fan speed is adjusted to keep the actual pressure
reading at setpoint. The static pressure setpoint is selected by determining the amount of pressure it
takes to produce air flow across a specific component. The components in a data center are normally a
perforated floor tile or a contained hot / cold aisle.
Figure 57 Senor placement
Static pressure control in a data center has been derived from the building air management systems
with the promises of a consist CFM or air flow from perforated floor tiles as they are added or removed
from the white space. Using static pressure to control fan speed within an air handler with VAV
(Variable Air Volume) systems has been applied successfully for many years. The key component that
allows the system to work so well within an air handler system is the VAV box. In this type of system
the VAV box controls the flow of air by adjusting a damper based on the local temperature that the
VAV box serves. As the VAV box opens and closes to maintain its zone temperature a secondary
control speeds up and slows down the supply fan to maintain a specific supply duct static pressure. As
the zone heats up, the damper opens which lowers the static in the duct and the fan speeds up. Keep
in mind that the zones are still controlled by temperature while the static pressure is only providing
the potential to flow air by keeping a higher pressure in the duct than the area being conditioned.
For a data center to be as effective using static pressure control to maintain fan speed each perforated
For a data center to be as effective using static pressure control to maintain fan speed each perforated
floor tile would need to act as a VAV damper box. Unfortunately, many of the data centers operating
today do not have automatically adjusting dampers that adjust the air flow from each perforated tile.
Without the VAV part of the system, a raised floor data center application becomes a manual process
Without the VAV part of the system, a raised floor data center application becomes a manual process
to fine tune perforated tile locations based on server CFM demand. Static pressure control is also very
dependent on the sensor position under the floor as floor obstructions like piping and cables can affect
static pressure readings. In addition CRAH unit location and perforated tile placement can cause
vortexes under the floor that would also affect the static pressure readings.
Understanding the limitations for static pressure to automatically adjust the fan speed based on the
Understanding the limitations for static pressure to automatically adjust the fan speed based on the
IT equipment demand should prompt an initial CFD (Computational Fluid Dynamics) evaluation of
the site to determine high and low pressure areas under the floor. In addition CFD’s should be
performed when the floor tile arrangement changes or the IT equipment demand changes. The under
floor environment will also change based on the floor tile arrangement changes and may not relate to
above floor air flow expectations. The SixSigma
®
and Tile Flow
®
simulations in the next sections will
illustrate under floor airflow in relation to tile flow and how the two variables change based on a unit
being turned Off or in standby.
Racks with Equipment
CRAH
CRAH