4.3.6 Connecting the CANbus cable at the Unit and Securing the CANbus Cable to Ground
The grounding wire on the CANbus cable must be used to ensure reliable communication. Connect 
the ground wire to the metal frame of the unit. The CANbus cable ground wire must be connected to 
an unpainted metal area of the unit chassis.
Connecting the CANbus sensors may require working in the high voltage electrical compartment of 
the cooling unit.
Figure 75 Install grounding ring connector
!
WARNING
Risk of electrical shock. Can cause injury and death.
Disconnect local and remote power supplies before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included 
and check the name
®
 microprocessor does not isolate power from the unit, even in the Unit 
Off mode.
Some internal components require and receive power even during the Unit Off mode of the 
Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch 
contains live high voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote 
disconnect switch. Refer to the unit electrical schematic.
Follow all local codes.
Existing grounding 
screw location to be 
reused for CANbus 
cable grounding ring.