Gas Control Assembly to the Thermal Well (cont’d) 
Step 8. 
To resume operation, follow the instructions located on the water heater 
lighting instruction label.  Or, use the lighting instructions located in the water heater 
installation and operating manual.
Flammable Vapor Sensor Testing 
Step 1. 
Move the gas control power switch to the “OFF” 
position.
Step 2. 
Disconnect the flammable vapor sensor harness from 
the gas control. 
Step 3. 
Using a multi-meter set to the ohms setting, measure 
the resistance of the flammable vapor sensor and resettable 
thermal switch.  The resistance must be between 3,000 and 48,000 
ohms.  If the resistance is out of this range, verify that the 
resettable thermal switch has not been tripped.  If it hasn’t, replace 
the thermal switch. 
120 VAC Circuit Trace 
Step 1. 
Verify 120VAC and proper polarity are at the wall outlet. 
Step 2. 
With the water heater plugged in and the gas control power switch in the 
“ON” position verify LED status. 
Flammable Vapor Sensor Testing 
CAUTION
Do not use standard multi-meter probes for this testing.  Doing so will damage the con-
nector.  Use special pin type electronic probes or small diameter wire pins inserted into
connector.
Gas control power 
switch 
Flammable vapor 
sensor harness 
27