Bosch Appliances Home Security System D7412G Manual De Usuario

Descargar
Página de 142
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 57
Bosch Security Systems | 1/04 | 47775E
Print Log
Default:
P
Selection:
Blank, E, or P
#22 Print Event Log (MENU FUNCTION only)
Use this function to print all the events stored in the
control panel starting at the start date and ending
with the last event in the log.
User Cmd 7
Default:
P
Selection:
Blank, E, or P
#23 User COMMAND 7 [COMMAND][7]
Use this function to activate an alarm programmed
in COMMAND 7 in the RADXPNTS Handler.
User Cmd 9
Default:
P
Selection:
Blank, E, or P
#24 User COMMAND 9 [COMMAND][9]
Use this function to activate an alarm programmed
in COMMAND 9 in the RADXPNTS Handler.
Bypass a Pt
Default:
P
Selection:
Blank, E, or P
#25 Bypass a Point [COMMAND][0]
Use this function to bypass individual points that are
P## Bypassable
. Points within the scope of the
command center can be bypassed where the
function is entered (see Section 2.10.1 Cmd Cntr
(Command Center) Assignment
).
The control panel ignores alarms/troubles and does
not display point faults when a point is bypassed.
Unbypass a Pt
Default:
P
Selection:
Blank, E, or P
#26 Unbypass a Point [COMMAND][0][0]
Use this function to unbypass individual points that
are programmed either 
P## FA Retrnable
 or 
P##
Bypass Returnable
. Points within the scope of the
command center can be unbypassed where the
function is entered (see Section 2.10.1 Cmd Cntr
(Command Center) Assignment). 
The control panel
responds to alarms/troubles and displays point faults
when a point is unbypassed.
Reset Sensors
Default:
E
Selection:
Blank, E, or P
#27 Reset Sensors [COMMAND][4][7]
Use this function to activate the Reset Sensors
function for Fire or Intrusion points programmed as
P## Resettable
 in Section 4.1 Point Index. Points
within the scope of the command center where the
function is entered resets (see Section 2.10.1 Cmd Cntr
(Command Center) Assignment
).
Change Relay
Default:
P
Selection:
Blank, E, or P
#28 Change Relays [COMMAND][5][4]
Use this function to manually set and reset Relays 1
through 128 (1 through 64 in a D7412G) installed in
the system.
Remote Program
Default:
P
Selection:
Blank, E, or P
#29 Remote Programming [COMMAND][4][3]
Use this function to initiate RAM sessions. When the
phone is ringing at the control panel, initiating this
function causes the control panel to seize the line.