D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS
EN | 90
Bosch Security Systems | 1/04 | 47775E
P## Fire Point
Default:
No
Selection:
Yes or No
Yes
This point is a Fire point.
No
This point is not a Fire point.
Use this option to make a 24-hour point a Fire point.
This option makes this point the highest priority
event in the control panel when an alarm occurs for
both reporting and displaying on the command
center.
Characteristics of a Fire Point
Reporting:  When a group of events
occur, the control panel routes and prints
out Fire Reports first.
Visual Annunciation: 
FIRE TROUBLES
continues to scroll until the trouble is
cleared. Once acknowledged, a 
FIRE
TROUBLE
 scroll lets the end user know
that a Fire point, or group of Fire points, is
still in trouble. Panel Wide Relays,
Summary Fire, and Summary Fire Tbl
activates if a relay is assigned when any
Fire point goes into alarm or is in trouble.
Audible Annunciation: A Fire point
activates the A# Fire Bell relay
programmed in Relay Parameters. The
amount of time and pattern of the relay
activation is programmed by area in Bell
Parameters,
 A# Fire Time, and A# Fire
Pat
.
Supervisory: A Fire point can send a Fire
Supervisory Report and activate the
Summary Fire Sup and Summary Fire
Tbl 
Panel Wide Relays with a P##
Response
 of 8-9-A-B-C.
Alarm Verification: A Fire point can delay
an alarm by the time programmed in A#
Verify Time
 in the Area parameters.
Reset Sensor: A fire device that requires
resetting can be manually reset using the
reset sensor relay for the area where it is
assigned.
Fire Walk: Fire points can be tested in the
system using the Fire Walk Test which
automatically resets each point for five
seconds when it is tripped and rings the
Fire Bell for two seconds.
You should dedicate a fire annunciation
device to all your Fire points if they are
assigned to a single area in a multiple area
system. Special red command centers and
annunciators with specific keys for fire
systems are designed for this type of
application (D1256 and D1257).
Do not use the Cross point function for
Fire points.