White Rodgers 1F56N-911 Single Stage Setpoint Thermostat Referencia De Cableado

Descargar
Página de 1
www.white-rodgers.com
9
TECHNICAL HELP
1C20/1C21/1C26/
1D56/1E56/1F56
RH
W
B
O
Y
G
RC
A
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
Heat
Relay
Compressor
Relay
Fan
Relay
*
* *
Factory or Field-Installed Jumper
Single transformer heating/cooling system
*
* *
Terminal energized
in cooling
Terminal energized
in heating
Terminal "A" is not 
for field wiring. See 
SPECIAL SYSTEM 
CONFIGURATIONS 
section for proper 
use of terminal "A".
Two-transformer heating/cooling system
RH
W
B
O
Y
G
A
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
Heat
Relay
Compressor
Relay
Fan
Relay
*
* *
*
* *
Terminal energized
in cooling
Terminal energized
in heating
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
RC
NOTE:  Remove  factory- 
installed jumper between 
RC and RH terminals for 
this application.
Terminal "A" is not for field wiring. 
See SPECIAL SYSTEM 
CONFIGURATIONS section for 
proper use of terminal "A".
Single transformer, single stage heat pump system
W
B
O
Y
G
A
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
Compressor
Relay
Fan
Relay
*
* *
Factory or Field-Installed Jumper
*
* *
Terminal energized
in cooling
Terminal energized
in heating
RH
Field-Installed Jumper
RC
Terminal "A" is not for field wiring. 
See SPECIAL SYSTEM 
CONFIGURATIONS section for 
proper use of terminal "A".
.18
.25
.3
.4
.2
.15
1.
.8
.6
.5
Arrow points to the
matched current rating
of the primary control
Move this lever to
adjust heat
anticipator
Anticipator adjustment
L
O
N G E R C
Y
C
L
E
S
Electric Heat Furnaces
(Single Transformer Systems Only)
The thermostat as shipped may not operate the fan correctly. If 
both the heating and cooling system must operate the fan relay, 
remove the yellow factory-installed jumper wire from the Y terminal 
and connect it to the A terminal. The fan should now cycle when the 
termostat calls for either heat or cool.
Heat Pump Applications
This thermostat WILL NOT provide multi-stage heating or cooling 
operation. For single-stage heat pump applications, install a short 
jumper wire across terminals W and Y. If the old thermostat has a 
terminal that is continuously energized, disconnect the wire from the 
old thermostat’s terminal and connect it either to the: ) B terminal, 
if the reversing valve is energized on a call for heat: or to the 2) O 
terminal, if the reversing valve is energized on a call for cool. If the 
system heats on a call for cool, or vice versa, this wire has been 
connected to the wrong terminal.
Special Application Terminals
The B and O terminals can provide switching for special functions 
other than heat pump operation. When the system switch is in the 
HEAT position, the B terminal is energized. When the system switch 
is in the COOL position, the O terminal is energized.
CONFIGURATION
TYPICAL WIRING DIAGRAMS
NOTE: Some thermostat
models don’t include all
terminals as shown here.
CONFIGURATION AND
TYPICAL WIRING