White Rodgers 36H SERIES Manual De Usuario

Descargar
Página de 12
PART NO. 37-6632B
Replaces 37-6632A
0927
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE IN-
STALLING  OR  OPERATING THIS  CONTROL  COULD  CAUSE  PERSONAL  INJURY 
AND/OR PROPERTY DAMAGE.
The 36H series combination gas valve is designed with redundant and main solenoid valves that control gas flow to the main 
burners, a pressure regulator to maintain a constant outlet pressure, and a two position on/off switch for electrical shutoff. 
Model numbers below include features as described: 
DESCRIPTION
SPECIFICATIONS
36H SERIES
Combination Gas Valve
INSTALLATION INSTRUCTIONS
CONTENTS
Description  .................................................................  1
Specifications  .............................................................  1
Precautions  ................................................................  2
Installation  ..................................................................  3
 
System Wiring
Adjustment  .................................................................  4
 
Pressure Regulator Adjustment
Lighting Instructions ....................................................  6
Type of Gas: 
Natural Gas
Ambient Temperature:   -40° to 175°F
Pressure Rating: 
14” W.C. (
1
2
 PSI) max.
Voltage: 
24 VAC
Frequency: 
50/60 Hz
Current: 
Single Stage - .410A
 
Two-Stage - .540A
MOUNTING POSITIONS:
Upright, or 0
° to 90° from upright
UPRIGHT
LEFT or RIGHT
INLET BOSS
VERTICAL 
Figure 1. Gas valve mounting positions
360˚
Model 
No.
# of 
Stages
Open
Characteristics
Proven
Pilot
36H22
1
Fast
NO
36H23
1
Slow
NO
36H32
1
Fast
YES
36H33
1
Slow
YES
36H54
2
Fast
NO
36H55
2
Slow
NO
36H64
2
Fast
YES
36H65
2
Slow
YES
Pressure Regulator Setting: (“ W.C.)
Single 
Stage
Two Stage
Low
High
Min Diff.
Low to High
Natural Gas 2.5 - 5.0 1.0 - 3.5
2.5 - 5.0
1.5
LP Gas
7.0 - 12.0 4.0 - 9.5 8.0 - 12.0
2.5
PIPE SIZES/CAPACITIES
Pipe Sizes 
Available (inches)
Capacity (BTU/hr) at 1”
pressure drop across valve
AGA Std. Nat. Gas
(1,000 btu/cu. ft.)
LP. Gas 
(2,500 btu/cu. ft.)
3/4” x 3/4” NPT 
300,000
486,000
1/2” x 3/4” NPT 
260,000
421,000
1/2” x 1/2” NPT
170,000
275,400
www.white-rodgers.com
www.emerson.com