Utica Boilers SFE IV Steam Instruccion De Instalación

Descargar
Página de 24
7
5. 
When the boiler is installed in a confined space and 
all air is provided from the outdoors, the confined 
space shall be provided with two permanent openings, 
one commencing within 12 inches from the top and 
one commencing 12 inches from the bottom of the 
enclosure. The openings shall communicate directly, or 
by ducts, with the outdoors or spaces (crawl or attic) 
that freely communicate with the outdoors. One of the 
following methods must be used to provide adequate 
air for ventilation and combustion.
A.  When directly communicating with the outdoors, 
each opening shall have a minimum free area of 1 
square inch per 4,000 BTU per hour of total input 
rating of all equipment in the enclosure. (Figure 
#4)
B.  When communicating with the outdoors by means 
of vertical ducts, each opening shall have a 
minimum free area 1 square inch per 4,000 BTU 
per hour of total input rating of all appliances in the 
enclosed space. (Figure #5)
C.  If horizontal ducts are used, each opening shall 
have a minimum free area 1 square inch per 2,000 
BTU per hour total input rating of all appliances in 
the enclosed space. (Figure #6)
D.  When ducts are used, they shall be of the same 
cross sectional area as the free area of the area of 
the openings to which they connect. The minimum 
dimension of rectangular air ducts shall not be less 
than 3 inches.
6. 
In calculating free area using louvers, grills or screens 
for the above, consideration shall be given to their 
blocking effect. Screens used shall not be smaller than 
1/4 inch mesh. If the free area through a design of 
louver or grill is known, it should be used in calculating 
the size opening required to provide the free area 
specified. If the design and free area is not known, it 
may be assumed that wood louvers will have 20-25% 
free area and metal louvers and grills will have 60-75% 
free area. Louvers and grills shall be fixed in the open 
position or interlocked with the boiler so that they are 
opened automatically during boiler operation.
Figure #4
Figure #5
Figure #6
VENTILATION AND COMBUSTION AIR