8 - COMBUSTION AIR AND VENT PIPE
Allowable Vent and Air Intake Lengths
3” Pipe Min. Length
3” Pipe Max. Length
15 ft. equivalent length
100 ft. equivalent length
FIELD INSTALL 2” BY 3”
 TRANSITION IN THE 
VERTICAL POSITION 
ONLY (2 REQ’D, NOT 
FURNISHED)
3”  INTAKE AND 
EXHAUST 
TERMINATIONS
2” (50.8MM) 
CPVC
 VENT PIPING
 (FURNISHED &
 REQUIRED)
2” (50.8MM) 
COMBUSTION AIR 
INTAKE PIPING 
(FURNISHED)
Figure 4 - Combustion Air & Vent Piping
9. 
Combustion air must be clean outdoor air. Do not take 
combustion air from inside structure because that air 
is frequently contaminated by halogens, which includes 
fluorides, chlorides, phosphates, bromides and iodides. 
These elements are found in aerosols, detergents, 
bleaches, cleaning solvents, salts, air fresheners, paints, 
adhesives, and other household products.
10. 
Locate combustion air inlet as far away as possible from 
swimming pool and swimming pool pump house.
11. 
 All combustion air and vent pipes must be airtight and 
watertight. 
12. 
Pitch exhaust air piping back to boiler at minimum ¼” per 
foot from vent terminals so all moisture in vent piping 
drains to boiler. Pitch pipes with no sags or low spots 
where moisture can accumulate and block flow of flue gas. 
13. 
Vent connections serving appliances vented by 
natural draft shall not be connected into any portion 
of mechanical draft systems operating under positive 
pressure.
8.2 Vent/Air Intake Termination Location
Consider following when determining appropriate location 
for termination of combustion air and vent piping. 
A. Position termination where vent vapors will not 
damage plants/shrubs, air conditioning equipment, or 
siding on the house.
B. Position termination so it will not be effected by wind 
eddy, air born leaves, snow, or recirculated flue gases.
C. Position termination where it will not be subjected to 
potential damage by foreign objects, such as stones, 
balls, etc.
D. Position termination where vent vapors are not 
objectionable.
E.  Put vent on wall away from prevailing winter wind. 
Locate or guard vent to prevent accidental contact 
with people or pets.
F.  Terminate vent above normal snow-line. Avoid locations 
where snow may drift and block vent. Ice or snow may 
cause boiler to shut down if vent becomes obstructed.
G.  Under certain conditions, flue gas will condense, 
forming moisture, and may be corrosive. In such 
cases, take steps to prevent building materials at 
vent from being damaged by exhaust of flue gas.
H.  United States - Terminate vent system at least 4 
feet (1.22 m) horizontally from, and in no case 
above or below, unless a 4 feet (1.22 m) horizontal 
distance is maintained, from electric meters, gas 
meters, regulators and relief equipment.
I.  Canada - Terminate vent system at least 6 feet 
(1.83m) horizontally from, and in no case above 
or below, unless 6 feet (1.83m) horizontal distance 
is maintained, from electric meters, gas meters, 
regulators and relief equipment.
J.  Terminate venting system at least 3 feet (0.3m) 
above any forced air inlet (except boiler’s 
combustion air inlet) within 10 feet (3m). 
K.  Terminate venting system at least 12 inches 
(300mm) from any air opening into any building. 
L.  Locate bottom of vent at least 12 inches (300mm) 
above grade. 
M.  Terminate vent not less than 7 feet (2.1m) above 
adjacent public walkway. 
N.  Vent terminal shall not be installed closer than 3 feet 
(0.9m) from inside corner of L shaped structure.
O.  Termination of vent should be kept at least 3 feet 
(0.9m) away from vegetation. 
P.  If multiple terminations are used, minimum of 
12 inches (300 mm) between exhaust of one 
termination and air intake of next termination. See 
pages 14 & 15.
Q.  All field installed vent pipe must be 3”.
Length of pipe is counted from end of supplied 2” CPVC 
pipe exiting boiler. Termination is not counted in “Total 
Equivalent Length.”
Reduce maximum vent/air intake length by 5 feet per each 
90° elbow.
WARNING
Covering non-metallic vent pipe and fittings with 
thermal insulation shall be prohibited.
!
  
13