Utica Boilers UB95M-200 Instruccion De Instalación

Descargar
Página de 52
• High limit control is mounted in ½” NPT control well 
and ¾” X ½” bushing on top of front boiler section at 
hot water outlet. 
• High limit control is tied in with boiler control and is 
factory set at 180°F (82°C) water temperature. 
• High limit setpoint is field adjustable and may be set 
anywhere between 100°F (38°C) and 180°F (82°C), 
with maximum high limit setpoint not exceeding 180°F 
(82°C). Field high limit setpoint adjustment for each 
installation depends on heating system requirements. 
• High limit control automatically resets when boiler water 
temperature decreases below high limit setpoint value 
by differential setpoint value. Adjustable differential from 
5°F (3°C) to 30°F (17°C).
• Boiler operating temperature (temperature curve) is 
calculated and set in boiler control parameters.
11.13 Casting Temperature Safety Switch
• Casting temperature safety switch, 230°F (110°C)
setpoint, shuts off power to boiler control in event of 
boiler lack of or loss of water. 
• Casting temperature safety switch is installed on top of 
aluminum boiler section behind supply piping. 
• Failure code is displayed on digital readout. Fault 
requires manual reset of casting temperature safety 
switch to restart boiler. Press reset on user interface 
panel also. 
• Verify boiler is properly filled with water and no air is 
trapped in top of casting (check cap on Cam Vent at 
heat exchanger) before resetting. 
 WARNING
Burn and scald hazard.  Never run cold water into a 
hot, empty boiler. Failure to follow these instructions 
could result in death or serious injury
!
     
11.14 
Circulator Pump
• Circulating pump moves water through closed loop 
supply and return piping systems, terminal heating 
equipment (finned tube radiators, etc.) and back 
through boiler for reheating. 
• Properly size circulator pump to overcome frictional 
losses (usually measured in feet of water, also referred 
to as “pump head loss”) of supply and return piping 
systems and boiler to provide required hot water flow 
rates. 
• Circulator pump is furnished in carton within boiler 
cabinet. 
• Locate circulator(s) on downstream (“pumping away”) 
side of expansion tank.
11.15 Blocked Vent Safety Assembly
Blocked vent safety assembly incorporates two pressure 
switches designed to discontinue operation of boiler if there 
is a problem with blower or venting system. 
The normally open switch closes upon initiation of blower 
and functions as air proving switch. 
The normally closed switch opens if there is a blockage in 
combustion air intake or exhaust vent pipes.
11.16 Drain Valve
Manual drain valve drains water in heating system, 
including boiler, hot water supply and return piping systems 
installed above drain valve. 
Drain valve is installed in return piping at bottom front of 
boiler section. Any piping installed below elevation of drain 
valve requires additional drain valves to be installed at low 
points in piping system in order to drain entire system.
 WARNING
Burn and scald hazard.  Safety relief valve could       
discharge steam or hot water during operation.       
Install discharge piping per these instructions.
!
     
11.17 Safety Relief Valve
• Each boiler must have a properly sized and installed 
American Society of Mechanical Engineers (ASME) rated 
safety relief valve. 
• Furnished  safety relief valve automatically opens at 30 
psig pressure to relieve strain on boiler and heating 
system from increasing pressure. 
• Pipe Safety relief valve discharge with same size pipe 
as valve discharge opening to open drain, tub or sink, 
or other suitable drainage point not subject to freezing. 
11.18 External Condensate Pump (optional)
For installations where there is no floor drain or other 
appropriate drainage receptacle available to receive 
condensate from boiler, external float activated condensate 
pump with integral sump is required. Condensate pump can 
be piped to remote tie in point to sanitary sewer system. 
For this application, boiler must be installed so that proper 
pitch of piping to external condensate reservoir (sump) can 
be accomplished. Use wood frame or concrete blocks to 
raise boiler as required for proper installation.
11.19 Concentric Vent/Air Intake Termination 
(Optional)
Optional concentric vent/air intake termination utilizes 
single opening per each appliance through wall or roof of 
structure.
11 - CONTROLS AND ACCESSORIES
22